High side MOSFET outputs + Ethernet module with 8/16/32/48/64 digital inputs/outputs (Modbus TCP-compatible)
High-side MOS outputs or relay contacts combined with digital optocoupler inputs form the basis of this module variant. Ideal for controlling valves or pumps, as well as for acquiring typical PLC signals. Connectivity is provided via Ethernet, USB, or Wi-Fi. Modbus TCP-compatible, with a rugged aluminum housing and flexible configuration for modern control tasks.
Price range: € 463,91 through € 2.348,51 Incl. 19% VAT plus shipping
Our promise to you
Product Description – module with High-side MOSFET outputs
High-side MOSFET outputs or relay contacts combined with digital optocoupler inputs form the basis of this module variant. The devices provide reliable switching performance of up to 3 A per channel while simultaneously acquiring AC signals via galvanically isolated optocoupler inputs. This makes them ideal for demanding automation tasks where safe signal isolation and robust load switching are required.
The modules can be flexibly integrated into existing control architectures via Ethernet, USB, or integrated WiFi. Modbus TCP ensures seamless integration into PLC, SCADA, and industrial control systems.
Functions such as event control, M2M communication, counters, flip-flops, and timeout protection enable autonomous and secure operation directly within the device. Typical applications include controlling solenoid valves, pumps, or motor starters, as well as building automated test systems.
The durable aluminum housing with DIN rail mounting ensures long service life and high operational reliability—ideal for industrial environments.
Flexible network communication via Ethernet & Wi-Fi
The Ethernet and WiFi interfaces of the BSW-OR8-64 enable flexible integration into existing networks—both wired and wireless. Via Ethernet (10/100 Mbps), the module with High-side MOSFET outputs can be operated with a static or dynamic IP address and accessed directly through standard network protocols, while WiFi allows wireless integration, for example via WPS or manual configuration.
Both communication methods support access through an integrated web interface as well as driver libraries and a mobile app, enabling simple parameterization and remote control. A key feature is the ability to make the module with High-side MOSFET outputs accessible across the entire network and operate it via browser, software tools, or mobile devices.
Overall, Ethernet and WiFi provide scalable and location-independent communication within industrial applications.
Simple direct connection via USB thanks to plug & play
The USB interface of the BSW-OR8-64 is primarily designed for a direct, local connection between the module and a control computer and is characterized by simple commissioning. Thanks to plug-and-play functionality and appropriate drivers, the device is automatically recognized, allowing immediate access to the module with High-side MOSFET outputs via software tools.
Technically, the interface is based on USB 2.0 with transfer rates of up to 480 Mbit/s, providing a stable and fast data connection for configuration and control. It is often used for initial setup or for applications where no network infrastructure is available.
Overall, USB provides a straightforward and reliable interface for direct access.
Optional CAN and serial interfaces for industrial communication
The optional CAN and serial interfaces extend the module with classic industrial fieldbus and point-to-point communication capabilities. Through the CAN interface, robust real-time data transmission can be achieved with configurable baud rates, standard or extended IDs, and selectable operating modes. A key feature is the integrated automatic CAN TX/RX mode, in which defined messages are transmitted and received cyclically or event-driven without requiring continuous control by higher-level software.
The configuration of TX/RX behavior is conveniently handled via the ICT-Tool, allowing transmission and reception logic to be easily parameterized. In addition, an open register protocol is available, enabling both CAN and serial data to be read and written directly.
The serial interface (e.g., RS-232 or RS-485, depending on the adapter) also supports configurable communication parameters such as baud rate, data bits, parity, and stop bits, making it suitable for integration into existing automation or legacy systems.
Both optional interfaces can be configured via a setup tool and permanently stored in the BSW-OR8-64 device memory, ensuring that communication automatically resumes after a restart. This makes them particularly well suited for autonomous applications and distributed systems without permanent PC connectivity.
Control & software
For control purposes, the module with High-side MOSFET outputs provides open protocols (TCP/IP, Modbus TCP, and HTTP), enabling flexible integration into existing IT and automation environments. These protocols allow both traditional industrial applications and modern IoT scenarios to be implemented directly, without the need for additional gateways or proprietary interfaces.
In addition, comprehensive API libraries are available for C, C++, C#, Java, VB, and other programming languages, enabling the functions of the BSW-OR8-64 to be seamlessly integrated into custom software solutions.
The DELIB driver library, including CLI tools, also enables fast and straightforward commissioning as well as direct control via scripts or the command line, which is particularly useful for test, automation, and development environments. Furthermore, the I/O Control App for mobile devices provides a convenient way to remotely control and monitor the system over the network, without requiring a traditional PC application.
Overall, this creates a highly flexible control architecture ranging from low-level integration to mobile operation.
Flexible CAN control via auto TX/RX and DELIB command mode
The control of the BSW-OR8-64 is based on two operating modes: the Auto TX/RX mode and the DELIB command mode. In Auto TX/RX mode, the module can automatically send and receive CAN messages without the need for a permanently connected control PC. This enables autonomous operation within a CAN network.
Alternatively, the DELIB command mode provides direct register-based access via a manufacturer-specific CAN protocol, where targeted commands are transmitted to the module. Read and write operations are implemented using defined CAN IDs and structured data packets, allowing highly flexible and precise control.
Configuration of these control modes is conveniently performed via the integrated USB interface on a PC. Using the corresponding tool, parameters such as communication behavior, TX/RX logic, and DELIB command structures can be easily configured and tested. This allows the module with High-side MOSFET outputs to be quickly adapted to different applications and efficiently integrated into existing CAN systems.
Structured protocol control for flexible system integration
The control of the BSW-OR8-64 is carried out via a structured, command-based protocol that enables direct communication with higher-level control systems or PCs. Commands for configuration, querying, and parameterization are transmitted via the serial interface and are clearly interpreted by the module with High-side MOSFET outputs.
Thanks to the modular structure of the protocol, easy integration into existing software and PLC environments is possible. Communication can be either cyclic or event-driven, allowing flexible adaptation to different applications.
Overall, this control approach enables precise and reliable operation as well as seamless integration of the module into industrial automation systems.
Galvanically isolated digital inputs with filtering functions for reliable signal acquisition
The digital inputs on the BSW-OR8-64 are implemented as opto-isolated switching inputs, ensuring reliable galvanic isolation between the field side and the internal electronics. They are designed for industrial 24 V AC/DC signals and enable safe detection of switching states even in electrically noisy environments. The integrated filtering function suppresses short interference pulses, ensuring stable signal processing.
In addition, the inputs feature event detection that reliably captures signal transitions and makes them available for further processing. In combination with counter and flip-flop functions, even fast pulses or state changes can be evaluated precisely. Each input of the BSW-OR8-64 is also equipped with an individual status LED that visually indicates the current switching state directly on the device, enabling fast on-site diagnostics.
As a result, the digital inputs are ideally suited for industrial automation tasks where robust and reliable signal acquisition is required.
Digital outputs with selectable load and switching technology (1A, 3A & MOSFET)
The digital outputs of the BSW-OR8-64 are available in different switching technologies depending on the version, each optimized for specific load types and applications. In the 1A variant, relay contacts are used, providing galvanically isolated mechanical switching and making them particularly suitable for general-purpose AC and DC loads in the lower power range.
The 3A variant is also based on relay technology but offers higher current-carrying capability, making it suitable for more robust loads and industrial applications where higher switching power is required.
The MOSFET version, in contrast, operates entirely electronically without moving contacts and is ideal for fast, wear-free switching in DC applications. It enables efficient control of resistive and inductive loads with high switching frequency and low power loss.
By combining these three variants, the module with High-side MOSFET outputs can be flexibly adapted to a wide range of requirements—from classic switching tasks to high-speed electronic applications.
Each individual output also features its own status LED, which directly visualizes the current switching state on the device.
Event Control – event-based automation
The Event Control function enables direct, event-driven processing of both digital and analog signals in the module with High-side MOSFET outputs, without requiring cyclic polling by higher-level software. Digital signal transitions can immediately trigger internal actions, while analog signals can generate events based on defined thresholds, measurement ranges, or significant value changes. This allows responses to be implemented much faster and more resource-efficiently compared to traditional polling-based processing.
The event logic can be flexibly configured, enabling both simple switching conditions and more complex dependencies between digital and analog signals. In addition, functions such as filtering, hysteresis, and threshold monitoring are available to ensure stable and reliable trigger conditions.
As a result, Event Control is particularly well suited for automation applications where signals must be evaluated intelligently and processed immediately.
M2M communication – direct device-to-device networking
The M2M (machine-to-machine) function enables direct communication between multiple modules or systems without a central control unit. States and events can be automatically exchanged and synchronized between devices, allowing the creation of distributed and autonomously operating automation structures. Communication is carried out via defined protocols and can be flexibly integrated into existing system architectures. As a result, M2M is particularly well suited for connected industrial and IoT applications.
Robust design with an industrial-grade enclosure and plug-in ready connection solution
The module with High-side MOSFET outputs is housed in a compact, industrial-grade enclosure designed for use in control cabinets and technical environments. The robust construction reliably protects the electronics against mechanical influences while enabling space-saving installation, typically on a DIN rail or comparable mounting system.
For electrical connection, pluggable, industry-standard screw or spring-clamp terminals from Wago are used, ensuring secure and vibration-resistant wiring. The clearly structured terminal layout significantly simplifies installation and maintenance, especially in complex systems.
The design of the BSW-OR8-64 is complemented by easily accessible status indicators and clearly labeled interfaces, supporting commissioning and on-device diagnostics. Overall, the form factor is consistently optimized for industrial robustness, easy integration, and service-friendly handling.
Integration and Operational Safety
The BSW-OR8-64 is a robust solution for industrial applications that require reliable processing of digital signals. Thanks to stable drivers, clear documentation, and the ICT diagnostic tool, the module can be quickly integrated into existing systems. The galvanically isolated electronics, “Made in Germany,” ensure high operational reliability, while regular updates and direct developer support enable long-term, stable use in professional environments.
Technical Specifications
The digital I/O PLC module features 16 digital inputs and 16 digital outputs (relays or MOSFETs), a USB 2.0 interface with a data rate of up to 480 Mbit/s, and optionally expandable interfaces such as CAN or RS-232. The power supply ranges from +7 V to +24 V DC. Integrated 16-bit counters, configurable input filters, and a fail-safe mode ensure reliable operation. The device is designed for DIN rail mounting.
Ethernet interface:
- Ethernet 10/100 Mbps
- Supported protocols: HTTP, UDP, TCP, DHCP, Modbus-TCP
- Control: API for Windows and Linux (DELIB driver library), command line interface, open TCP protocol, Modbus-TCP
- Encrypted Ethernet communication possible
- Open standard or Modbus TCP protocol
- Web interface and app (smartphone and tablet)
Wi-Fi interface:
- Wi-Fi connection available
- WPS feature
- WPS Button
USB interface:
- USB 2.0 interface up to 480 Mbit/s
- Quick setup thanks to plug-and-play integration
- Control: API for Windows and Linux (DELIB driver library), command-line interface
CAN interface:
- Interface can be retrofitted as an option
- CAN interface according to ISO 11898
- Open CAN protocol (RAW CAN)
- Automatic transmit/receive mode
- Electrically isolated up to 500 V
RS-232 interface:
- Interface can be retrofitted as an option
- RS-232 interface with up to 115,200 baud
Relay outputs 1 A:
- Type: Normally Open (NO)
- Max. switching voltage: 36 V AC / DC
- Max. switching current: 0.5 A AC / DC
- Max. load current: 1 A AC / DC
- Max. switching power: 10 W
- Timeout protection function (configurable via software)
- Status LED for each output
Relay outputs 3 A:
- Type: Normally Open (NO)
- Max. switching voltage: 48 V AC / DC
- Max. switching current: 3 A AC / DC
- Max. conduction current: 3 A AC / DC
- Max. switching power: 90 W
- Timeout protection function (configurable via software)
- Status LED for each output
MOSFET outputs 1 A:
- Type: P-channel
- Max. switching voltage: 16 V DC
- Min. switching voltage: 5 V DC
- Max. switching current: 1 A DC
- Max. switching power: 16 W DC
- Timeout protection function (configurable via software)
- Status LED for each output
MOSFET outputs 3 A:
- Max. switching voltage: 36 V DC
- Min. switching voltage: 2.8 V DC
- Max. switching current: 3 A DC
- Max. switching power: 108 W DC
- Timeout protection function (configurable via software)
- Status LED for each output
Digital inputs:
- Selectable between 16, 32, 64, 96, and 128 channels
- Type: AC/DC optocoupler
- Signal level: ±5 V to ±15 V or ±15 V to ±30 V
- 16-bit counter per channel (up to 100 Hz)
- Detects a transition from low to high and from high to low (flip-flop)
- Status LED for each channel
Additional features:
- Configurable event control
- M2M functionality
- General
- Technical data
- ICT-Tool
- Configuration
- Configuration CAN
- Configuration serial
- Modbus
- M2M
- Event-Control
- Controlling CAN
- Controlling serial
- DELIB-API commands
- WEB interface
- App
- Connection examples
- Connectors
- Downloads & manuals
- Scope of delivery
- Accessories
Digital inputs
Digital signal states can be recorded with our optocoupler inputs. Input and output circuits are electrically isolated from each other up to 2.5 kV.
Digital-in input filter
With our digital-in modules, an input filter can be set in a time interval of 1 ms...255 ms for filtering interference pulses.
Counter
Each input has a 16-bit counter.
Detection of state changes
Status changes that occur between readout cycles are reliably recorded by internal status change flip-flops and can be read out separately via software. In addition, such an event is signaled by a status LED.
Relay
Our digital outputs use power relays with normally open (NO) function.
All our relays are equipped with a software-based timeout protection function to protect against damage caused, for example, by contact breakage to the control PC.
Fail-Safe Mode
The Fail-Safe mode is a safety function in which the DEDITEC module switches to a previously configured, safe switching state in the event of a connection failure.
This is intended to prevent connected installations or systems from continuing to run in an uncontrolled manner.
USB interface with Plug & Play
Thanks to Plug & Play, our modules with USB interface are automatically recognized and are immediately ready for use without any configuration. Configuration is only required if several USB modules from the same product series are used on the same system.
WEU modules
WEU modules (WEU = WiFi, Ethernet, USB) can be connected to the PC network by cable via Ethernet or USB interface, but also via WiFi. For a more user-friendly connection setup via WiFi, the module can also be connected to the router using the WPS function.
Automatic transmit and receive mode
Use our Auto TX/RX mode and automate the workflow of your DEDITEC product by automatically processing or sending CAN packets from other participants in the network. With our free ICT-Tool, you can define how the TX and RX packets should be processed via a graphical user interface.
Plug connector
A screwless system from the manufacturer WAGO® Kontakttechnik is used as the connector. The 1-wire female connectors are 100 % protected against mismating and have an ejection and locking mechanism.
LEDs
Each digital input and output has a separate LED that lights up when the signal status is active. The status of the operating voltage, communication with the interface, error events or the occurrence of a timeout can also be displayed.
M2M
Machine-to-machine, or M2M for short, involves direct communication between two or more modules. Analog or digital input signals from one transmitter module can be automatically transmitted to another module on a channel-by-channel basis.
M2M transmission is supported by all our products in the WEU series or by products with a CAN interface.
Event-Control
This function can be used to implement small control tasks that are saved in the module. These control tasks are configured as events and actions and then executed automatically according to the “if-then” principle.
Software and control for programmers
Our supplied DELIB driver library makes it easy to address the product via our API in almost all programming languages under Windows and Linux.
We offer support for the following programming languages:
- C
- C++
- C#
- VB
- VBA
- VB.Net
- Java
Remote switching of IP modules
Our IP modules can be conveniently and easily controlled worldwide via the TCP-IP network. The following options are available to you.
DEDITEC I/O Control app
With our DEDITEC I/O-Control app, our modules can also be controlled remotely. All you need is the network configuration of the module. The app is available for iOS and Android smartphones.
Web interface
Our IP modules can be operated from any browser. All you need is the IP address of the module.
M2M
Our WEU series modules can establish direct M2M communication with any DEDITEC Ethernet product, enabling, for example, the automated transmission of measured values or remote monitoring of machines and systems.
ICT-Tool
With the help of our all-in-one ICT-Tool software, you can configure, update, control and test your DEDITEC modules quickly and easily. The tool is included in the DEDITEC driver library.
More security through encryption
With the DEDITEC encryption mode, all TCP communication from the control PC to the DEDITEC module can be encrypted. This prevents unauthorized access to the module via TCP by third parties.
Control modules via Modbus TCP
Modbus TCP enables standardized data exchange between controllers, measuring devices, drives, and higher-level systems, regardless of the manufacturer. Status and measured values are read or written via the open Modbus register protocol.
Command-Line-Interface
With the help of the command line interface, or CLI for short, our products with Ethernet or USB interface can be easily addressed via the command line. Our digital and analog inputs/outputs are supported. The CLI is available for Windows and Linux operating systems.
General information
| Power supply | + 7 V DC ... +24 V DC |
|---|---|
| LEDs |
|
| DIN rail mounting | 35 x 7,5 mm |
| Operating temperature | +10 °C ... +50 °C |
Special features
| M2M-function | The M2M function makes it possible to automate data exchange between our modules. After configuration using our ICT tool, the transmitter and receiver modules can communicate with each other without additional user software and transmit measurement data independently. |
|---|
| Event-Control | With our event control, you have the option of linking occurring events to a specific action. With the help of our ICT tool, the control tasks can be stored directly in the module memory thanks to an intuitive “if-then” logic. Monitor, control and regulate without an additional control PC. |
|---|
Fail-Safe-function
| FAIL-SAFE-function |
|
|---|---|
| Timeout-mode "Normal" | The "Normal mode" is valid once and must be reactivated manually by software command after each timeout event. The customer application still has access to all controller outputs. |
| Timeout-mode „Auto reactivate“ | In “Auto reactivate mode”, the timeout function is automatically reactivated once communication with the control PC has been re-established. The customer application still has access to all outputs of the control unit. |
| Timeout-mode "Secure Outputs" | The “Secure outputs mode” blocks access to the outputs after the timeout event. Unlocking can only be carried out by software command. This is an important safety aspect in the event of a fault. |
Interfaces
CAN Interface
| CAN-Interface |
|
|---|
Ethernet Interface
| Ethernet-interface |
|
|---|---|
| Connection setup |
|
| IP-address | DHCP or static |
| WPS button | Activation WPS |
| DIP switches |
|
| Access speed |
|
USB Interface
| USB-Interface |
|
|---|
RS-232 Interface
| RS-232 Interface |
|
|---|
Inputs/Outputs
Digital outputs (MOSFET)
| MOSFET 2A |
|
|---|
Digital outputs (relay)
| Relay up to 1 A |
|
|---|
Digital outputs (relay)
| Relay 3 A |
|
|---|
Digital inputs (optocoupler)
| Optocoupler |
|
|---|---|
| Input filter |
|
| Input counter |
|
| Flip-flops |
|
Connectors
| Plug connector 16-pin |
|
|---|
The ICT-Tool
Integration, configuration and testing - Our all-in-one Windows tool contains all the functions you need to put our products into operation quickly, easily and efficiently. Start with the setup and configuration, install firmware updates and use the extensive test and diagnostic options. The integrated help menu provides additional support if required.
Below you will find a brief overview of the program’s basic menus.
Module selection
Here you can integrate a new product into the ICT tool by clicking on the “+” symbol and then configure it.
ICT TreeView
In the TreeView, on the left-hand side of the program window, you can see the respective control elements or functions that are supported by your selected module. The scope of the functions depends on the respective product.
Overview
All relevant module information can be accessed here at a glance.
- Module name
- Module ID
- Firmware revision
- MAC address
- LAN and WiFi Network address (module dependent)
Inputs / Outputs
This overview shows the number of I/Os supported by your module.
Module infos
Here you will find all the important feature information for your module.
General features
Here you will find all the important feature information for your module.
Digital I/O features
Here you will find information about the digital I/Os supported by the module.
Analog I/O features
Here you will find information about the type of analog I/Os supported by your module.
Special I/O features
Here you will find information about the type of special I/Os supported by your module.
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
Info
All relevant module information can be called up here at a glance.
- Module name
- Module ID
- Firmware revision
- Interface type
- Current DIP switch setting (only for Ethernet modules)
Identification
If several DEDITEC Ethernet modules are active in the network, a signal LED on the selected module can be activated via an identification function. This facilitates visual assignment.
Restart
You can restart your module here. The module status shows whether the restart was successful.
USB configuration
If you want to use several USB modules from the same product series on one PC, each of these modules must first be assigned its own module number.
LAN info
On this information page, you will find the current LAN network information and all the settings for your module at a glance.
LAN configuration
Integrate the product into your network or control it directly via a 1-to-1 connection.
The following parameters can be changed.
- Board name
- DHCP on/off
- IP address
- Subnet mask
- Default gateway
- TCP Port
WiFi info
All important WiFi settings are displayed on this page
WiFi configuration
Here you can change the network settings of the selected WiFi product.
The following settings can be made:
- Board name
- WLAN on/off
- Router name
- Router password
WPS
With the WPS function, your module can be connected to the router quickly and easily, automatically (WPS on the router is required)
CAN configuration
With our CAN products in the BS, NET and UC series, settings for the interface and the TX/RX packets can be made using the ICT tool.
More information can be found here:
Serial configuration
For our serial products in the BS, NET, UC and RO series, changes to the interface can be made using the
ICT tool.
More information can be found here:
Modbus TCP
Here you can set the Modbus TCP configuration of the module.
The following configurations can be made.
- Enable/disable access via Modbus TCP
- TCP port
TCP encryption
Here you can make settings for the encryption of your module.
The following configurations can be made.
- Allow unencrypted protocol
- Allow “User” encryption mode
- User password
- Allow “Admin” encryption mode
- Admin password
NTP configuration
You can make changes to the NTP service here.
The following configurations can be made.
- NTP service on/off
- server
- Port
- Timezone
WEB-Login
Here you can change the login settings of the web interface.
The following configurations can be made.
- Session duration
- Login name
- Login password
- Allow I/O access via web interface
D/A Default Values
Here you can set the D/A values and modes with which the module should be started.
The value and mode can be set individually for each channel.
Watchdog configuration
Here you can make and save settings on your watchdog stick.
Save or Load config
Using the “Save or Load config” function, you can save your entire module configuration in an external XML file.
This means you can always load your module in the desired original state.
The following configurations can be saved depending on the module type.
- USB configuration
- LAN configuration
- WiFi configuration
- TCP encryption
- NTP configuration
- Serial configuration
- CAN configuration
Status
This gives you an overview of the activity of the transmitter and receiver module
The following information from the transmitter module is displayed:
- Status of the activity: If the check mark is set, this action is currently being performed.
- Total number of actions performed. Is reset to 0 after a restart of the module.
- Number of actions per second.
- Number of DELIB errors that occur when executing commands from the DEDITEC driver library.
The following information from the receiver module is displayed:
- Connected: If the check mark is set, the transmitter and receiver modules are connected.
- IP address of the receiver module.
- Number of connection attempts.
Receiver modules
You can set the network settings of the receiver module here.
The following settings can be made
- Name for the receiver module
- Network settings of the receiver module
- Timeout
- Encryption type/ password
Action
With an action, you define which input signal is to be sent from the transmitter module to which output of a receiver module.
The following settings can be made:
- Type of task (digital, analog)
- Which receiver module should be used
- The interval at which the operations are to be carried out
- Start channel of the transmitter module
- Number of channels to be transmitted
- Start channel of the receive module
In the image on the right, DI data is sent every 100ms from channel 3(CH Start) to channel 8 ((CH Start) + (CH Count)) to channels 0-5 of the target module.
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
Status
The Status area provides an overview of all active events and executed actions.
The following information is listed:
- Event number
- Event type
- Time interval of the event
- Number of events that have occurred
- Action number
- Number of triggered actions
- Number of other actions
Events configuration
Up to 16 different events can be created in the configuration menu. An event can be used, for example, to define switching thresholds at the analog inputs or logical states at the digital inputs of the module and link them to an executable action. The configuration itself is saved permanently in the module configuration memory of the module.
The following event modes are available, depending on the module type:
- DI: High-Low state of a digital input.
- DI flip-flop: Status change of a digital input (is stored in the module with the so-called flip-flop flag and deleted again after readout).
- DO readback: ON-OFF status of a digital output (is read out using a DO readback command).
- A/D: Current or voltage level at the analog inputs
Configuration actions
Up to 16 different actions can be created in the configuration menu. An action defines what should happen within an event after a condition is met.
The following action modes are available, depending on the module type:
- Set DO output: Switches a digital output on or off
- Set D/A output: Outputs a current or voltage value at an analog output
- Send CAN packet: A special CAN TX event is triggered (up to eight CAN TX events can be configured separately).
Digital Out
Hier können Sie die digitalen Ausgänge Ihres Modules ein- und ausschalten.
Folgende Funktionen können in dieser Form getestet werden.
- Kanalweise Ein- und Ausschalten der digitalen Ausgänge
- Readback der Kanäle
- Setzen eines Digitalausgangs für eine bestimmte Zeit (Modulabhängig)
- Gibt an welchen Status die Kanäle nach Ablauf der Zeit einnehmen sollen (Modulabhängig)
- Testen der Ausgänge
Digital Out
All digital outputs of your product can be checked by clicking on the buttons.
The following switching options are possible:
- Switching on and off channel by channel
- Channel-by-channel switching on or off for a specific time (product-dependent)
- Reading back the switching status (readback)
Digital In
In this view, the logical states of all optocoupler inputs can be read out.
The following information is displayed:
- Logical status of the inputs (ON/OFF)
- Number of detected pulses (counter function)
- Change of state detected (flip-flop)
TTL I/O
In this menu, the TTL channels of the module can be configured as inputs or outputs. The individual TTL outputs can be switched on or off by pressing the buttons. In addition, the status of all TTL inputs can be read out.
The tool offers the following functions:
- Configuration of the channels as input or output (in blocks of 8)
- Switching on and off channel by channel
- Reading back the switching status (output readback)
- Displaying the logical status of the inputs (input readback)
Analog Out
Here you can test the analog outputs of the module and manually enter any voltage or current value.
Analog In
In this menu, voltage or current values of all A/D channels can be displayed.
It is also possible to activate our A/D software filter with different filter levels.
CAN Runtime Parameter
Here you can change the CAN settings of the interface, the RX and TX packets in runtime.
The following settings can be made:
- Baud rate
- Extended ID
- Active on/off
- CAN ID
- Mode
CNT48
Here you can read out the counter readings of a counter module, select filter options and set various counting modes.
The following counting modes are supported:
- Read on rising edge
- Read on rising edge x2
- Read on rising edge x4
- Period duration
- Frequency measurement
- PWM measurement
Pulse generator
The pulse generator can be used to generate square-wave signals. High and low time as well as the number of pulses can be set here.
PWM Out
In this menu you have the option of testing various PWM frequencies. In addition, the duty cycle can be entered manually for each individual channel.
Temp
The temperature of all connected temperature sensors is displayed here directly in °C.
Graphical display
This menu allows a graphical representation of all analog input signals, such as A/D, temperature or FIFO-IN.
Watchdog
This tool can be used to check the configured watchdog parameters for correct function.
I/O – Timeout
You can use the timeout function in the I/O area to simulate a timeout case for your module.
The following is a description of the timeout window
- Read / Write symbol: Flashes to indicate an active connection to the module
- Automatic access: Removing the tick triggers a timeout after the timeout time has expired
- Manual access: Manual retrieval of data from the module
- Timeout status: Shows whether the timeout is active and whether a timeout event has occurred
- Timeout mode: Selection between 3 timeout modes, Normal, Reactivate and Secure
- Timeout duration: The time after which the timeout should be triggered is set here
- Activate / deactivate: Activates or deactivates the timeout function
Access times tests
You can test the access times for the module here. The following access time tests can be performed:
- Register – Read/Write/Write + Readback
- Digital I/O – Read/Write/Write + Readback
- Analog I/O – Read/Write/Write + Readback
Access times tests
This test can be used to determine the access times to the module. The test values are read and written in 8, 16, 32, or 64-bit commands.
Access times Register
The following example checks the register accesses to an Ethernet module. The average access time here is 0.5 ms.
Access times Analog I/O
In the following example, the access times to an Ethernet module with analog I/Os are checked. The average access time here is 0.6 ms.
Access times Digital I/O
In the following example, the access times to an Ethernet module with digital I/Os are checked. The average access time here is 0.6 ms.
Cable feedback tests
For this test, the digital or analog outputs of the module are connected to the corresponding digital or analog inputs of the module via cable. The feedback test now checks whether the output and input values match.
Cable return test
The cable return test can be used to check the function of all digital and analog inputs and outputs (I/Os) of a module. To do this, inputs and outputs are wired together externally on a 1:1 basis. The test software analyzes whether the output signals arrive correctly at the inputs, thereby identifying wiring errors or hardware defects.
Analog test
In analog test mode, the D/A converter outputs defined test voltages, which are then read in by the A/D converter and compared with the target values. The software counts the number of test runs and automatically documents any deviations.
Digital test
In the digital test, the switching states of the relay or MOSFET outputs are fed back externally to the optocoupler inputs. Here, too, the software counts and compares the number of cycles and automatically detects transmission errors or deviations.
Cable return test
The cable return test can be used to check the function of all digital and analog inputs and outputs (I/Os) of a module. To do this, inputs and outputs are wired together externally on a 1:1 basis. The test software analyzes whether the output signals arrive correctly at the inputs, thereby identifying wiring errors or hardware defects.
Analog test
In analog test mode, the D/A converter outputs defined test voltages, which are then read in by the A/D converter and compared with the target values. The software counts the number of test runs and automatically documents any deviations.
Digital test
In the digital test, the switching states of the relay or MOSFET outputs are fed back externally to the optocoupler inputs. Here, too, the software counts and compares the number of cycles and automatically detects transmission errors or deviations.
A/D ripple
The ripple test displays the residual ripple of the individual A/D inputs.
A/D quality measurements
The quality of an A/D measurement is influenced by various factors and can be affected by external interference. A reliable method for checking measurement quality is to measure a stable battery voltage. Our diagnostic tools can be used to determine the residual ripple and noise behavior.
A/D ripple
The A/D ripple test can be used to measure the residual ripple of the individual A/D inputs and check for interference signals such as mains hum or voltage instabilities.
A/D noise
The noise behavior of each A/D channel can be displayed graphically using A/D noise measurement. Additional filter stages with averaging can be used to smooth and improve the measurement signal.
FIFO In/Out
The software FIFO test can be used to specifically test the integrated FIFO buffering of our digital and analog NET I/O modules. Depending on whether it is an input or output module, data is read from the submodule FIFO or written to the submodule FIFO.
FIFO settings
The submodule number can be used to specify which module is to be tested. The start and end channels can also be used to transmit several channels simultaneously. In addition, the transmission frequency can be set and the desired FIFO mode selected – for example, for the use of test values or the actual measured values of the module.
All important information at a glance
During program execution, key information such as the size of the data packets, free and occupied bytes in the FIFO buffer, the number of data packets sent or received, and the current FIFO status are clearly displayed.
D/A output test
The D/A output test enables targeted testing of each individual D/A channel of a module. A freely selectable test voltage can be output directly. Currently, simple square wave signals with configurable high and low times are available. The signals can be monitored simultaneously with an oscilloscope. This function is also ideal for long-term tests. The test software detects DELIB errors and logs them automatically.
Mustertext
Mustertext
DO 4* value + wait
In this test, adjustable 16-bit values are written to the digital outputs of the module.
The values are sent to the module using the DapiDOSet16 command. The start channel is always channel 0.
You can set different wait times between the individual calls.
The test is intended for testing the functionality of the module.
Mustertext
Mustertext
Modbus I/O test
In the diagnostics section of the ICT-Tool, you can test the module’s digital and analog inputs and outputs directly via Modbus TCP. Register addresses as well as transfer and return values are displayed in a debug panel, allowing you to quickly diagnose problems with the D/A converter, for example. A complete overview of all register addresses and examples can be found in the Modbus manual at the following link:
To benefit from the latest functions and prevent errors, we recommend that you always keep your DEDITEC product up to date.
Flash Files
Downloading the firmware flash file package via the ICT tool
- Go to Flash Files in the “Firmware update” menu
- Click on the download button to start the download.
- Administration rights are required for the automatic unpacking of the flash files. If these rights are not available, the files are downloaded to the download area of your PC and must be extracted manually to the installation directory.
\DEDITEC\DELIB\programs\flash_files
Downloading the firmware flash file package via the DEDITEC homepage
- Download the required firmware flash file package from our homepage: Downloads -> Software -> Firmware
- Extract the files to the following installation path: ..\DEDITEC\DELIB\programs\flash_files
Flash modules
In the “Firmware update” menu, select the module you want to update and then click on the “Flash modules” or “Flash submodules” button.
The firmware is now updated and the module is then restarted automatically.
Information on the firmware flasher
The following information is displayed in the firmware flasher:
- Last FW: Displays the last firmware version
- Current FW: Displays the currently installed firmware version
- Newest FW: Displays the latest firmware version
- Log: Displays status or error messages during the flash process
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
General
Here you can make general configurations to the ICT tool.
The following changes can be made:
- Language – setting between German and English possible
Updates
Here you can search for available DELIB or firmware updates.
- Automatic update search at program start
- Search for DELIB updates
- Search for firmware updates
Error log
Here you can make settings for the deditec_debug.log. This is saved under the path C:\Users\?USER?\AppData\Local\DEDITEC.
The following settings can be made:
- Enable writing to the debug.log
- Activate log notifications
- Activate automatic deletion of the debug.log
- Setting after how many days the debug.log should be deleted
- Set the maximum size of the debug.log
DELIB – DebugView – Global
Settings can be made here for the information that is to be displayed with the DebugView.
- Activate debug output
- Activate display of errors
DELIB – DebugView – Details
More detailed settings can be made here for the information to be displayed with the DebugView.
Configuration of our modules via the Ethernet / WiFi and USB interface
Depending on the product series, different interfaces are available for configuration with the control PC.
(Dynamic IP)
(Static IP)
In order to be able to address the DEDITEC product via Ethernet, it must be provided with the corresponding network settings. The following options are available for configuration:
- USB
- Ethernet / Dynamic IP
- Ethernet / Static IP
- Web interface
- WiFi
Connect the DEDITEC module to your PC via USB cable. Thanks to the Plug & Play function and the DELIB driver library, our modules are automatically recognized by your computer’s operating system. You can now access the module with our ICT-Tool and make the network settings in the configuration menu.
In DHCP mode, the DEDITEC module is automatically assigned a free IP address and the appropriate network settings by a DHCP server. The following options are available for activating DHCP mode:
- Activation via DIP switch
- Activation via the network search function in the “Edit / Add menu” of the ICT-Tool
- Activation via the “Module configuration menu” of the ICT-Tool
- Activation via the web interface of the module
DHCP mode can be activated on all DEDITEC modules with DIP switch 1.
In the “Edit / Add menu” of the ICT-Tool, you can scan the network for connected DEDITEC modules. Any modules found are then displayed in a list view where they can be configured and saved.
Click on the “Edit” button in the line of the desired module.
You can now make the desired network configuration in the following window and save it in the module using the “Save / Test” button.
To access the module’s configuration menu, the module must first be integrated into the ICT-Tool.
As the factory IP settings of the module often do not match the network settings of the customer’s PC, the following options are available to help you change them:
- Integration via the USB interface
- Integration via DHCP with DIP switch 1
- Direct connection to the PC * IP factory setting via DIP switch
- Integration via WiFi
Integration via the USB interface (only if available)
Connect the DEDITEC module to your PC via USB cable. Thanks to the Plug & Play function and the DELIB driver library, our modules are automatically recognized by your computer’s operating system. You can now select the module in the main menu of the ICT-Tool and make the network settings in the configuration menu.
Integration via DHCP using DIP switch 1
Set DIP switch 1 on your module to “ON” and switch the module on.
The module now starts in DHCP mode and can be added or selected as a module in the ICT-Tool. You can now make the network settings in the configuration menu. Then reset DIP switch 1 again.
Integration via the IP factory settings with DIP switch 3 and crossover cable
Connect the DEDITEC module directly to your PC using a crossover cable. Set the module’s DIP switch 3 to “ON” and switch the module on. The module now starts with the factory IP address 192.168.1.1. Temporarily set your PC to the same 192.168.1.x network and then add the DEDITEC module in the ICT-Tool.
You can now change the network settings of the module in the configuration menu. DIP switch 3 and the PC IP settings are then reset.
Integration via WiFi (only for WEU series modules)
By pressing the CFG button on the DEDITEC module, you activate the WPS function to automatically connect to the WLAN router of your network (see “WiFi” tab). After a successful connection, the module can be called up in the ICT-Tool via the board name stored in the router – e.g. “boardname.fritz.box” – and can be added as a new module. You can then make the network settings in the configuration menu. For support, contact your system administrator if necessary.
The module is now set to DHCP on the software side.
Central network settings, such as IP configuration or DHCP activation, can be made via the module’s web interface.
To call up the web interface of the module, start your Internet browser and enter the IP address of the module in the URL line. -> For more details, see the “Web interface” tab
To integrate the module into an existing network, it can be permanently assigned a fixed IP address. The following options are available for configuring the module’s network settings:
- Configuration via the network search function in the “Edit / Add menu” of the ICT-Tool
- Configuration via the “Module configuration menu” of the ICT-Tool
- Configuration via the module’s web interface
In the “Edit / Add menu” of the ICT-Tool, you can scan the network for connected DEDITEC modules. Any modules found are then displayed in a list view where they can be configured and saved.
Click on the “Edit” button in the line of the desired module.
You can now make the desired network configuration in the following window and save it in the module using the “Save / Test” button.
To access the module’s configuration menu, the module must first be integrated into the ICT-Tool.
As the factory IP settings of the module often do not match the network settings of the customer’s PC, the following options are available to help you change them:
- Integration via the USB interface
- Integration via DHCP with DIP switch 1
- Direct connection to the PC * IP factory setting via DIP switch
- Integration via WiFi
Integration via the USB interface (only if available)
Connect the DEDITEC module to your PC via USB cable. Thanks to the Plug & Play function and the DELIB driver library, our modules are automatically recognized by your computer’s operating system. You can now select the module in the main menu of the ICT-Tool and make the network settings in the configuration menu.
Integration via DHCP using DIP switch 1
Set DIP switch 1 on your module to “ON” and switch the module on.
The module now starts in DHCP mode and can be added or selected as a module in the ICT-Tool. You can now make the network settings in the configuration menu. Then reset DIP switch 1 again.
Integration via the IP factory settings with DIP switch 3 and crossover cable
Connect the DEDITEC module directly to your PC using a crossover cable. Set the module’s DIP switch 3 to “ON” and switch the module on. The module now starts with the factory IP address 192.168.1.1. Temporarily set your PC to the same 192.168.1.x network and then add the DEDITEC module in the ICT-Tool.
You can now change the network settings of the module in the configuration menu. DIP switch 3 and the PC IP settings are then reset.
Integration via WiFi (only for WEU series modules)
By pressing the CFG button on the DEDITEC module, you activate the WPS function to automatically connect to the WLAN router of your network (see “WiFi” tab). After a successful connection, the module can be called up in the ICT-Tool via the board name stored in the router – e.g. “boardname.fritz.box” – and can be added as a new module. You can then make the network settings in the configuration menu. For support, contact your system administrator if necessary.
The module is now set to DHCP on the software side.
Central network settings, such as IP configuration or DHCP activation, can be made via the module’s web interface.
To call up the web interface of the module, start your Internet browser and enter the IP address of the module in the URL line. -> For more information, see the “Web interface” tab
All central network settings for the module can be made via the module’s web interface.
Access to the web interface
To call up the web interface of the module, start your Internet browser and enter the IP address of the module in the URL line. The access data is set at the factory as follows:
| IP address: | 192.168.1.1 |
| User name: | admin |
| Password: | admin |
If you do not know the IP address of the module, simply use the network search function in the “Edit / Add Men” of the ICT-Tool or look at the IP address assignment in your router.
You can also find more information on this under the “Static IP” or “Dynamic IP” tabs
All modules in the WEU series have an integrated WiFi interface. The connection to a WiFi network can be established either via the ICT-Tool or by pressing the CFG button on the module. You can then make further network settings in the configuration menu. The following options are available for establishing a WiFi connection:
- Establish WiFi connection via button
- Establish automatic connection via ICT-Tool (WPS)
- Establish manual connection via ICT-Tool
By pressing the CFG button on the DEDITEC module, you activate the WPS function to automatically connect to the WLAN router of your network.
Different modes are activated depending on the duration of operation:
- 3–6 Press and hold for seconds: Activate WiFi
- 7–12 Press and hold for seconds: Start WPS connection
- 13–15 Press and hold for seconds: Deactivate WiFi
A status LED on the module indicates the current mode by flashing.
WPS – Simple connection to the network
WPS (WiFi Protected Setup) makes it particularly easy to connect to a WLAN network – without having to enter a network name or password manually.
This is how the WPS connection works:
- Activate WPS mode on the module (press the CFG button for 7-12 seconds)
- Press the WPS button on the router within 2 minutes*.
- The connection is now established automatically.
* Note:
For this type of connection to work, the router used must support WPS. Otherwise, the WLAN connection must be set up manually via the LAN configuration in the ICT-Tool.
A connection to the router can be established automatically in the WPS tab. To do this, press the “WPS Start” button and activate the WPS function on the router within two minutes. The devices will then connect to each other automatically.
If the router login data is known, a connection can be established in the WiFi configuration tab by entering the user name and password. Please note that WiFi must also be activated.
Configuration of CAN modules
The parameters of the CAN interface can be fully configured via the ICT-Tool. In addition to the baud rate, CAN address and other settings, automatic send and receive packets can also be set up.
Automatic transmission (TX mode)
The Auto-TX mode allows cyclical transmission of data packets, optionally with analog or digital input states to other CAN addresses. Alternatively, a trigger event can also be defined. In this case, a data packet is only sent once a data packet has been received on a certain CAN ID (e.g. CAN sync on ID 0x80).
Automatic receiving (RX mode)
With Auto-RX mode, on the other hand, received data packets are forwarded directly to analog or digital outputs. For example, relay outputs can be set via another CAN bus subscriber.
ICT-Tool
The ICT-Tool can be used to quickly and easily read out or change CAN interface settings.
Status interface
Here you can find information about the status of the CAN interface
- Baud rate
- Module address
- Receiving address
- CAN status
- Extended ID
- CAN modus
Hier finden Sie Informationen über die TX / RX -Pakete
- Anzahl gesendeter / empfangener Pakete
- TX / RX – Pakete pro Sekunde
- Durchschnitt gesendeter / empfangener Pakete
Settings can be made on the CAN interface here.
- Baud rate
- Adress Bit-mode
- Module address
- Receiver address
Here you can configure the CAN settings of the connected submodules.
- A/D mode
- A/D filter
- D/A mode
- Counter mode
- Timeout
- CNT48 mode
- CNT48 submode
- CNT48 filter
Here you can make settings to the TX package configuration.
- activate / deactivate
- Trigger mode
- Interval
- Use extended ID
- Send to CAN-ID
- TX mode
You can make settings to the RX package configuration here.
- activate / deactivate
- Use extended ID
- Receive from CAN-ID
- RX mode
You can find more details on control and some programming examples in the programming section.
Configuration of our serial modules (RS-232 / RS-485)
To configure the serial interface, the module must be connected to the PC either via the Ethernet interface or USB interface.
The module can then be accessed and configured in the ICT tool.
The following parameters can be set:
- Preferred mode (115k baud, module address = deactivated, echo = off)
- Baud rate
- Module address (only for RS-485)
- Echo active on/off
- Text mode / Register mode
Changing the interface standard
Switch between RS-232 and RS-485 (applies only to NET and RO series)
The modules are configured for RS-232 operation as standard when delivered. The module can be switched to RS-485 operation by changing the jumper positions. Further information on this can be found in the manual for the respective product.
Control of Ethernet modules via Modbus TCP protocol
Modbus TCP is a protocol based on TCP/IP that is used for communication between different devices. It allows data to be read and written via so-called registers and bits. Standardized function codes are used for this purpose, such as:
General register allocation
| Modbus register (dez) |
Data type | Access | Data size (Bit) |
Description |
| 0 ... 9999 | Coil | write / read | 1 | Writing and reading back digital outputs |
| 10000 ... 19999 | Discrete Inputs | read | 1 | Read digital inputs |
| 30000 ... 39999 | Input Register | read | 16 | Read holder register |
| 40000 ... 49999 | Holding Register | write / read | 16 | Write and read back registers |
Control of Ethernet modules via Modbus TCP
Our modules can be controlled via the Modbus register protocol for quick and easy integration. This protocol allows you to conveniently read and write values, switch digital outputs, or query inputs. The complete protocol is available for download.
Example:
// Writes the digital outputs of channels 1-16
MASTER.WriteMultipleRegisters(SLAVE_ID, 0x0420, 0x03);
// Reads the values from channels 1-16
registerValue = MASTER.ReadHoldingRegisters(SLAVE_ID, 0x0420, NUMREGISTERS);
Configuration of our Modbus TCP modules
The Ethernet module is configured as follows at the factory:
Modbus active = YES
Modbus IP address = IP address of the module
Modbus port = 502 (standard Modbus port)
If you would like to use your own settings or deactivate the Modbus function, please use the configuration menu of our ICT-Tool.
Changing the parameters in the ICT-Tool
1. Setting/changing the IP address:
The IP address for Modbus TCP and TCP-IP is always identical.
Detailed instructions on how to change the IP address can be found at the following link:
2. Deactivate the Modbus function in the module:
If you want to deactivate the Modbus function, navigate to the “Modbus TCP” submenu, uncheck the “Enable” box, and then save your settings.
3. Port configuration
Modbus TCP communication takes place on port 502 by default. Alternatively, any port between 100 and 49151 can be set.
Modbus I/O test
In the diagnostics section of the ICT-Tool, you can test the module's digital and analog inputs and outputs directly via Modbus TCP. Register addresses as well as transfer and return values are displayed in a debug panel, allowing you to quickly diagnose problems with the D/A converter, for example. A complete overview of all register addresses and examples can be found in the Modbus manual at the following link:
M2M
Machine to Machine
M2M is the abbreviation for “machine-to-machine” and enables automatic data transmission between two or more devices. This means that analog or digital input signals from a transmitter module can be automatically transmitted to a receiver module, where they are immediately output again.
Data exchange without a control PC
The modules communicate directly at device level and therefore do not require any additional user software. The one-off configuration of the transmitter module can be carried out very easily using our ICT-Tool. All settings remain permanently stored in the module memory, even in the event of a power failure. After a restart, the module automatically switches back to M2M operation.
M2M Ethernet or M2M CAN
With our DEDITEC products, we differentiate between M2M Ethernet and M2M CAN. We also refer to the latter as CAN-TX/RX mode. Both M2M methods are supported by most of our modules with Ethernet or CAN interface.
M2M-Ethernet
To be able to use M2M-Ethernet, the transmitter module must always be equipped with our M2M feature, whereas the receiver module can be any DEDITEC product with an Ethernet interface.
A maximum of 4 receiver modules (destinations) can currently be configured and up to 8 actions defined.
Definition of the receiver module
- Designation/name of the module
- Network configuration of the module
- Timeout time
- Encryption type and password
Definition of actions
These actions are used to define which analog or digital inputs are to be transmitted to a receiver module.
The following parameters can be defined in an action:
- Which data should be sent (digital or analog)
- To which receiver module (destination) should be sent
- The interval with which the operations are to be performed
- Start channel of the transmitter module
- Number of input channels to be transmitted
- Start channel of the receiver module
In the image on the right, DI data is sent every 100ms from channel 3(CH Start) to channel 8 ((CH Start) + (CH Count)) to channels 0-5 of the target module.
M2M-CAN
All DEDITEC products with a CAN interface are equipped with the M2M-CAN feature. The “Auto TX/RX mode” can be set in the ICT-Tool via the configuration menu. Depending on the product type, 8(4) TX and 8(4) RX modes can be defined.
"TX modes" submenu
The pictures on the right show an example configuration for a transmitter module (TX mode) and a corresponding receiver module (RX mode).
The TX mode on the transmitter module sends the logical states of inputs 1-64 to CAN ID 0x700 every 500ms.
The RX mode on the receiver module receives data packets on CAN ID 0x700 and outputs these values to outputs 1-64.
General information on Event-Control
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
To make our modules even more customer-friendly and flexible and to make it easier for you to enter the world of automated control technology, we have implemented Event-Control as a new feature in our products. This function can be used to implement small control tasks that are stored in the module. These control tasks are configured as events and actions and then executed automatically according to the “if-then” principle.
Configuration in the ICT-Tool
The ICT-Tool can be used to configure and monitor 16 events and 16 actions.
Processing in the module
The events stored in the module are automatically monitored and processed by the CPU in the module after the module is started. As soon as the set condition (“event”) is fulfilled, the corresponding action is executed. This automatism in the module makes an additional control PC with associated user software superfluous.
Functions
The following actions, among others, can be combined with the Event-Control:
- Monitoring the analog and digital inputs (A/D, DI)
- Setting switching thresholds for analog inputs
- Switching the module outputs (relay, MOSFET, D/A)
- Sending CAN packages
We are constantly expanding the range of promotional options. We are also happy to implement your special customer requirements on request.
Modulauswahl
Hier können Sie Ihre Module mit einem Klick auf das „+“ Symbol ins ICT-Tool einbinden, um diese anschließend konfigurieren oder testen zu können.
Module series that support this function:
- BS-USB2 series
- BS-WEU series
- NET series
- UC series
- CAN-Box series
Module series that do not support this function:
- Starter series
- RO series
- COS series
ICT Treeview
Im Treeview auf der linken Seite des Programmfensters, sehen Sie die jeweiligen Formen, die von Ihrem Modul unterstützt werden.
Mit einem Klick können Sie sich diese Form dann im rechten Teil des Programmes anzeigen lassen und mögliche Konfigurationen oder Tests durchführen.
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
With the Event-Control module, you can react flexibly and automatically to external signals – directly on the I/O module, without a PC or additional controller.
How does it work?
The system registers external events, such as the switching of an input or the triggering of a sensor, and then executes predefined actions. These actions can be simple tasks such as switching on a relay or sending a CAN message.
The advantages:
-
Independent processing – Control takes place directly on the module, independently of the host system.
-
Flexibly customizable – you can link any inputs and outputs together.
-
Complex logic possible – Thanks to logical operators such as AND, OR or NOT, even more sophisticated controls can be implemented.
-
Simple configuration – events and actions are conveniently defined via our ICT-Tool and transferred to the module without any programming knowledge.
Example:
A digital input detects the opening of a door. The system then automatically switches on a light without a PC being involved.
Modulauswahl
Hier können Sie Ihre Module mit einem Klick auf das „+“ Symbol ins ICT-Tool einbinden, um diese anschließend konfigurieren oder testen zu können.
Modulserien, die von dieser Funktion unterstützt werden:
- BS-USB2-Serie
- BS-WEU-Serie
- NET-Serie
- UC-Serie
- CAN-Box
Modulserien, die von dieser Funktion nicht unterstützt werden:
- Starter-Serie
- RO-Serie
- COS-Serie
ICT Treeview
Im Treeview auf der linken Seite des Programmfensters, sehen Sie die jeweiligen Formen, die von Ihrem Modul unterstützt werden.
Mit einem Klick können Sie sich diese Form dann im rechten Teil des Programmes anzeigen lassen und mögliche Konfigurationen oder Tests durchführen.
Our ICT-Tool in the “Statistics” section provides a quick overview of all current campaigns and events.
Eine mini SPS
Um unsere Module noch kundenfreundlicher und flexibler zu gestalten und Ihnen den Einstieg in die Welt der automatisierten Steuer- und Regelungstechnik zu erleichtern, haben wir als neues Feature das sog. Event-Control in unsere Produkte implementiert. Mit dieser Funktion lassen sich kleine Steueraufgaben in das Modul speichern, die anschließend nach dem „Wenn-Dann“ Prinzip automatisch Aktionen ausführen.
The following information can be taken from the statistics:
- Executed event no.
- Event mode
- Interval
- Number of events executed
- Number of the executed action
- Number of actions performed
Modulserien, die von dieser Funktion unterstützt werden:
- BS-USB2-Serie
- BS-WEU-Serie
- NET-Serie
- UC-Serie
- CAN-Box
Modulserien, die von dieser Funktion nicht unterstützt werden:
- Starter-Serie
- RO-Serie
- COS-Serie
ICT Treeview
Im Treeview auf der linken Seite des Programmfensters, sehen Sie die jeweiligen Formen, die von Ihrem Modul unterstützt werden.
Mit einem Klick können Sie sich diese Form dann im rechten Teil des Programmes anzeigen lassen und mögliche Konfigurationen oder Tests durchführen.
An event is used to execute a specific action as soon as a condition is met.
A time period can also be specified for how long the condition must be fulfilled in order to execute an action.
These settings are saved directly in the Module-Configuration-Memory of the module.
Example: Voltages can be automatically output via the D/A converter or relays can be switched when a previously defined switching threshold is reached at the A/D inputs or a signal is detected at a digital input.
Depending on the features of your product, you can choose from different modes:
“DI” / “DI flip-flop” / “DO readback”
DI: High or low signal of a digital input.
Flip-Flop: If the status of the digital input changes, the flip-flop of the channel is set and then reset again.
DO-Readback: The status of the output channel is read out.
The following settings can be made:
- Number of the channel to be monitored
- Condition of the channel status (on = 1 / off = 0)
- Minimum time to wait until the action is triggered
- Number of the action to be executed (this is configured in the Action area)
“A/D”
The voltage currently present at the analog input is read out.
The following settings can be made:
- Number of the channel to be monitored
- A/D mode (selection depends on module)
- Condition that must be fulfilled (value greater than … , value less than … , value in a range)
- Values that must be achieved for the condition
- Minimum time to wait until the action is triggered
- Number of the action to be executed (this is configured in the Action area)
In the “Actions” section of our ICT-Tool, you define which tasks are to be performed automatically as soon as a condition (“event”) is fulfilled.
For example, you can specify that a certain CAN packet should be sent when a certain voltage is measured on an A/D channel or a signal is detected at a digital input.
Depending on the features of your product, you can choose from different modes:
Folgende Informationen können der Statistik entnommen werden:
- Ausgeführte Event-Nr.
- Event-Modus
- Intervall
- Anzahl ausgeführter Events
- Nummer der ausgeführten Aktion
- Anzahl ausgeführter Aktionen
“Set D/A output”
Outputs a voltage or a current at an analog output.
The following settings can be made:
- Number of the channel on which the action is to be executed
- D/A mode (selection depends on module)
- Voltage or current to be output
- Time to wait before executing the action again
“Set DO output”
Switches a digital output on or off.
The following settings can be made:
- Number of the channel to be controlled
- State (0 = off / 1 = on) that is to be set
- Time to wait before executing the action again
“Send CAN package”
The set CAN TX event is triggered. For this function, the trigger mode in the CAN TX package must be set to “TX-EVENT” (see configuration).
The following settings can be made:
- Number of the CAN TX event to be triggered
- Time to wait before executing the action again (prevents a CAN packet from being sent too frequently)
You can find more information on configuring TX mode here:
Control of our CAN modules
Our RAW CAN modules can be controlled in two ways:
1. Auto TX/RX mode
2. DELIB command mode
1. Auto TX / RX mode
This operating mode allows the module to process CAN packets automatically without the need for an additional control PC. Configuration is very simple using the ICT tool and requires no programming knowledge.
Automatic transmission (TX mode)
Auto-TX mode allows automatic, cyclical transmission of CAN packets to other bus participants. The module's digital and analog input signals can thus be forwarded directly to other devices.
As an alternative to cyclic transmission, trigger events can also be defined. This means that a CAN packet is only sent, for example, when a CAN message has been received on a specific CAN ID.
TX mode configuration
The following settings can be configured:
- Enable/disable TX mode
- Trigger mode
- Interval
- Use extended ID
- Send to CAN ID
- TX mode
Automatic receive (RX mode)
In Auto-RX mode, received data packets are forwarded directly to the analog or digital outputs of the module. For example, relay outputs can be set on the module via another CAN bus participant.
RX mode configuration
The following settings can be configured:
- Enable/disable RX mode
- Use extended ID
- Receive from CAN ID
- RX mode
2. DELIB command mode
In DELIB command mode, the module's registers are accessed via a CAN protocol developed by DEDITEC. The module expects the CAN messages on a CAN address specified in command mode. Read and write accesses with different data lengths (BYTE, WORD, LONG) are possible. Details on the protocol structure and register assignment can be found in the “Protocols & Register Assignment” manual in the download area.
Control of our RS-232 / RS-485 modules
There are two options available for controlling our RS-232 / RS-485 modules:
1. Register-based via an open protocol
2. Via plain text input via a terminal program
Please note!
We only recommend using the RS-485 interface in conjunction with a microcontroller and your own serial protocol.
1. Control via our open serial protocol
Serial control is register-based. An open communication protocol was created for this purpose, which is used to address the module's registers and thus execute read or write commands. The “Protocols & Register Assignment” manual describes the transmission and reception frames for communicating with RS-232/RS-485 modules.
2. Control via plain text using HyperTerminal
The digital inputs and outputs can be controlled or read directly via “plain text” using HyperTerminal. Examples of this can be seen in the adjacent illustration.
Management functions
DapiOpenModule
This function opens a specific module.
Description
This function opens a specific module.
Definition
ULONG DapiOpenModule(ULONG moduleID, ULONG nr);
Parameter
moduleID=Specifies the module to be opened (see delib.h)
nr=Specifies which module is to be opened.
nr=0 -> 1. Module
nr=1 -> 2. Module
Return value
handle=Corresponding handle for the module
handle=0 -> Module was not found
Remark
The handle returned by this function is required to identify the module for all other functions.
Programming example
// Open USB module
handle = DapiOpenModule(RO_USB1, 0);
printf(„handle = %x\n“, handle);
if (handle==0)
{
// USB module was not found
printf(„Module could not be opened\n“);
return;
}
DapiCloseModule
This command closes an open module.
Description
This command closes an open module.
Definition
ULONG DapiCloseModule(ULONG handle);
Parameter
handle=This is the handle of an open module
Return value
None
Programming example
// Close module
DapiCloseModule(handle);
DapiGetDELIBVersion
This function returns the installed DELIB version.
Description
This function returns the installed DELIB version.
Definition
ULONG DapiGetDELIBVersion(ULONG mode, ULONG par);
Parameter
mode=Mode with which the version is read out (must always be 0).
par=This parameter is not defined (must always be 0).
Return value
version=Version number of the installed DELIB version [hex]
Programming example
version = DapiGetDELIBVersion(0, 0);
//With version 1.32 installed
version = 132(hex)
DapiSpecialCMDGetModuleConfig
This function returns the hardware configuration (number of input and output channels) of the module.
Description
This function returns the hardware configuration (number of input and output channels) of the module.
Definition
ULONG DapiSpecialCommand(ULONG handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, par, 0, 0);
Parameter
handle=This is the handle of an open module
Querying the number of digital input channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI
Query number of digital input flip-flops
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI_FF
Query number of digital input counters (16-bit counter)
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI_COUNTER
Query number of digital input counters (48-bit counter)
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_CNT48
Querying the number of digital output channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DO
Querying the number of digital pulse generator outputs
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_PULSE_GEN
Querying the number of digital PWM outputs
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_PWM_OUT
Querying the number of digital input/output channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DX
Querying the number of analog input channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_AD
Querying the number of analog output channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DA
Query number of temperature channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_TEMP
Query number of stepper channels
par=DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_STEPPER
Return value
Querying the number of digital input channels
return=number of digital input channels
Query number of digital input flip-flops
return=number of digital input flip-flops
Query number of digital input counters (16-bit counter)
return=number of digital input counters (16-bit counter)
Query number of digital input counters (48-bit counter)
return=number of digital input counters (48-bit counter)
Querying the number of digital output channels
return=number of digital output channels
Querying the number of digital pulse generator outputs
return=number of digital pulse generator outputs
Querying the number of digital PWM outputs
return=number of digital PWM outputs
Querying the number of digital input/output channels
return=number of digital input/output channels
Querying the number of analog input channels
return=number of analog input channels
Querying the number of analog output channels
return=number of analog output channels
Query number of temperature channels
return=number of temperature channels
Query number of stepper channels
return=number of stepper channels
Programming example
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
//Returns the number of digital input channels
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DO, 0, 0);
//Returns the number of digital output channels
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DX, 0, 0);
//Returns the number of digital input/output channels
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_AD, 0, 0);
//Returns the number of analog input channels
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DA, 0, 0);
//Returns the number of analog output channels
ret=DapiSpecialCommand(handle,
DAPI_SPECIAL_CMD_GET_MODULE_CONFIG,
DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_STEPPER, 0, 0);
//Returns the number of stepper channels
DapiOpenModuleEx
This function specifically opens a module with an Ethernet interface. The parameters IP address, port number and the duration of the timeout can be defined.
Description
This function specifically opens a module with an Ethernet interface. The parameters IP address, port number and the duration of the timeout can be defined. The module is opened independently of the settings made in the DELIB Configuration Utility.
Definition
ULONG DapiOpenModuleEx(ULONG moduleID, ULONG nr, unsigned char* exbuffer, 0);
Parameter
moduleID = Specifies the module to be opened (see delib.h)
nr = Specifies which module (if several) is to be opened.
nr = 0 -> 1. Module
nr = 1 -> 2. Module
exbuffer = Buffer for IP address, port number and duration of the timeout
Return value
handle = Corresponding handle for the module
handle = 0 -> Module was not found
Remark
The handle returned by this function is required to identify the module for all other functions.
This command is supported by all modules with an Ethernet interface.
Programming example
// Open ETH-Module with parameter
DAPI_OPENMODULEEX_STRUCT open_buffer;
strcpy((char*) open_buffer.address, "192.168.1.10");
open_buffer.portno = 0;
open_buffer.timeout = 5000;
handle = DapiOpenModuleEx(RO_ETH, 0, (unsigned char*) &open_buffer, 0);
printf("Module handle = %x\n", handle);
DapiScanAllModulesAvailable
This function can be used to scan all modules connected to the USB bus.
Description
This function can be used to scan all modules connected to the USB bus.
The module ID and module no. of each module found are determined.
Definition
ULONG DapiScanAllModulesAvailable(uint nr)
Parameter
nr = 0: All modules connected to the USB bus are searched for
nr = i: Reading out the individual connected modules
Return value
Indicates the number of modules found.
Programming example
no_of_modules =
DT.Delib.DapiScanAllModulesAvailable(0);
for (i = 1; i <= no_of_modules; i++)
{
ret = DapiScanAllModulesAvailable(i);
moduleID = ret & 0x0000ffff;
moduleNr = (ret >> 16) & 0xff;
}
Register functions
DapiWriteByte
This command executes a direct register write command to the module.
Description
This command executes a direct register write command to the module.
Definition
void DapiWriteByte(ULONG handle, ULONG adress, ULONG value);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
value=Specifies the data value that is written (8-bit)
Return value
None
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Data is written to register 0x10
DapiWriteByte(handle, 0x10, 0xFF);
DapiWriteWord
This command executes a direct register write command to the module.
Description
This command executes a direct register write command to the module.
Definition
void DapiWriteWord(ULONG handle, ULONG adress, ULONG value);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
value=Specifies the data value that is written (16-bit)
Return value
None
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Data is written to register 0x10
DapiWriteWord(handle, 0x10, 0xFFFF);
DapiWriteLong
This command executes a direct register write command to the module.
Description
This command executes a direct register write command to the module.
Definition
void DapiWriteLong(ULONG handle, ULONG adress, ULONG value);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
value=Specifies the data value that is written (32-bit)
Return value
None
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Data is written to register 0x10
DapiWriteLong(handle, 0x10, 0xFFFFFFFF);
DapiWriteLongLong
This command executes a direct register write command to the module.
Description
This command executes a direct register write command to the module.
Definition
void DapiWriteLongLong(ULONG handle, ULONG adress, ULONGLONG value);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
value=Specifies the data value that is written (64-bit)
Return value
None
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Data is written to register 0x10
DapiWriteLongLong(handle, 0x10, 0xFFFFFFFFFFFFFFFF);
DapiReadByte
This command executes a direct register read command on the module.
Description
This command executes a direct register read command on the module.
Definition
ULONG DapiReadByte(ULONG handle, ULONG adress);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
Return value
Content of the register to be read (8-bit)
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programmierbeispiel
// Reads 8 bits from the address 0x0
ULONG data;
data = DapiReadByte(handle, 0x0);
DapiReadWord
This command executes a direct register read command on the module.
Description
This command executes a direct register read command on the module.
Definition
ULONG DapiReadWord(ULONG handle, ULONG adress);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
Return value
Content of the register to be read (16-bit)
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Reads 16 bits from the address 0x0
ULONG data;
data = DapiReadWord(handle, 0x0);
DapiReadLong
This command executes a direct register read command on the module.
Description
This command executes a direct register read command on the module.
Definition
ULONG DapiReadLong(ULONG handle, ULONG adress);
Parameter
handle=This is the handle of an open module
adress=Address to be accessed
Return value
Content of the register to be read (32-bit)
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Reads 32 bits from the address 0x0
ULONG data;
data = DapiReadLong(handle, 0x0);
DapiReadLongLong
This command executes a direct register read command on the module.
Description
This command executes a direct register read command on the module.
Definition
ULONGLONG DapiReadLongLong(ULONG handle, ULONG address);
Parameter
handle=This is the handle of an open module
address=Address to be accessed
Return value
Content of the register to be read (64-bit)
Remark
This should only be used by experienced programmers. This allows direct access to all available registers.
Programming example
// Reads 64 bits from the address 0x0
ULONGLONG data;
data = DapiReadLongLong(handle, 0x0);
Digital input counter
DapiDIGet1
This command reads a single digital input.
Description
This command reads a single digital input.
Definition
ULONG DapiDIGet1(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Indicates the number of the input to be read (0, 1, 2, 3, .. )
Return value
State of the input (0/1)
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
maxCh > ch
Programming example
// Read out 1 channel
unsigned long data;
data = DapiDIGet1(handle, 0);
DapiDIGet8
This command reads 8 digital inputs simultaneously.
Description
This command reads 8 digital inputs simultaneously.
Definition
ULONG DapiDIGet8(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the input from which to read (0, 8, 16, 24, .. )
Return value
State of the read inputs.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
maxCh > ch (ch must be 0, 8, 16, ...)
Programming example
// Read out 8 channels
unsigned long data;
data = DapiDIGet8(handle, 0);
DapiDIGet16
This command reads 16 digital inputs simultaneously.
Description
This command reads 16 digital inputs simultaneously.
Definition
ULONG DapiDIGet16(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the input from which to read (0, 16, 32, ...)
Return value
State of the read inputs.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
maxCh > ch (ch must be 0, 16, 32, ...)
Programming example
// Read out 16 channels
unsigned long data;
data = DapiDIGet16(handle, 0);
DapiDIGet32
This command reads 32 digital inputs simultaneously.
Description
This command reads 32 digital inputs simultaneously.
Definition
ULONG DapiDIGet32(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the input from which to read (0, 32, 64, ..)
Return value
State of the read inputs.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
maxCh > ch (ch must be 0, 32, 64, ...)
Programming example
unsigned long data;
// ----------------------------------------------------
// Read a value from the inputs (Eingang 1-31)
data = (unsigned long) DapiDIGet32(handle, 0);
// Chan Start = 0
printf("Input 0-31 : 0x%x\n", data);
printf("Press any key to continue\n");
getch();
// ----------------------------------------------------
// Read a value from the inputs (input 32-64)
data = (unsigned long) DapiDIGet32(handle, 32);
// Chan Start = 32
printf("Input 32-64 : 0x%x\n", data);
printf("Press any key to continue\n");
getch();
DapiDIGet64
This command reads 64 digital inputs simultaneously.
Description
This command reads 64 digital inputs simultaneously.
Definition
ULONGLONG DapiDIGet64(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the input from which to read (0, 64, ..)
Return value
State of the read inputs.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI, 0, 0);
maxCh > ch (ch must be 0 or 64)
Programming example
// Read out 64 channels
ULONGLONG data;
data = DapiDIGet64(handle, 0);
DapiDIGetFF32
This command reads the flip-flops of the inputs and resets them.
Description
This command reads the flip-flops of the inputs and resets them.
Definition
ULONG DapiDIGetFF32(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the input from which to read (0, 32, 64, ..)
Return value
Status of 32 input status changes.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI_FF
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI_FF, 0, 0);
maxCh > ch (ch must be 0, 32, 64, ...)
DapiDIGetCounter
This command reads the input counter of a digital input.
Description
This command reads the input counter of a digital input.
Definition
ULONG DapiDIGetCounter(ULONG handle, ULONG ch, ULONG mode);
Parameter
handle=This is the handle of an open module.
ch=Specifies the number of the input from which to read.
mode=0 (normal counting function)
mode=DAPI_CNT_MODE_READ_WITH_RESET (read counter and reset counter directly)
mode=DAPI_CNT_MODE_READ_LATCHED (read out the stored counter reading)
Return value
Output of the counter value.
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DI_CNT
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DI_COUNTER, 0, 0);
maxCh > ch
Programming example
value = DapiDIGetCounter(handle, 0 ,0); // Counter of DI Chan 0 is read
value = DapiDIGetCounter(handle, 1 ,0); // Counter of DI Chan 1 is read
value = DapiDIGetCounter(handle, 8 ,0); // Counter of DI Chan 8 is read
value = DapiDIGetCounter(handle, 0 ,DAPI_CNT_MODE_READ_WITH_RESET); // Counter of DI Chan 0 is read AND reset
value = DapiDIGetCounter(handle, 1, DAPI_CNT_MODE_READ_LATCHED); // Reading the stored meter reading from DI Chan 1
DapiSpecialCommand - DapiSpecialCounterLatchAll
This command saves the counter readings of all input counters simultaneously in a buffer (latch).
Description
This command saves the counter readings of all input counters simultaneously in a buffer (latch).
This allows all counter readings of the latch to be read out one after the other.
A special feature here is that it is possible to "freeze" the meter readings at the same time and the frozen readings (latch) can then be read out one after the other.
Definition
void DapiSpecialCommand(ULONG handle, DAPI_SPECIAL_CMD_COUNTER, DAPI_SPECIAL_COUNTER_LATCH_ALL, 0, 0);
Parameter
handle=This is the handle of an open module.
mode=DAPI_SPECIAL_CMD_COUNTER (It is a counter command)
mode=DAPI_SPECIAL_COUNTER_LATCH_ALL (Freezes all counter inputs and makes them available as a latch)
Remark
This command is only supported by our RO-O8-R8 time modules!
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_COUNTER, DAPI_SPECIAL_COUNTER_LATCH_ALL, 0, 0);
DapiSpecialCommand - DapiSpecialCounterLatchAllWithReset
This command saves the counter readings of all input counters simultaneously in a buffer (latch). In addition, the counter readings of the input counters are subsequently reset.
Description
This command saves the counter readings of all input counters simultaneously in a buffer (latch). In addition, the counter readings of the input counters are subsequently reset.
Definition
void DapiSpecialCommand(ULONG handle, DAPI_SPECIAL_CMD_COUNTER, DAPI_SPECIAL_COUNTER_LATCH_ALL_WITH_RESET, 0, 0);
Parameter
handle=This is the handle of an open module.
mode=DAPI_SPECIAL_CMD_COUNTER (It is a counter command)
mode=DAPI_SPECIAL_COUNTER_LATCH_ALL_WITH_RESET (Freezes all counter inputs and makes them available as a latch and resets the counter of the input channels)
Remark
This command is only supported by our RO-O8-R8 time modules!
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_COUNTER, DAPI_SPECIAL_COUNTER_LATCH_ALL_WITH_RESET, 0, 0);
DapiSpecialCommand - DapiSpecialDIFilterValueSet
This command sets a filter [ms] in which time interval digital input channels are sampled.
Description
This command sets a filter [ms] in which time interval digital input channels are sampled.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FILTER_VALUE_SET, ULONG time_ms, 0);
Parameter
handle=This is the handle of an open module
time_ms=Time interval [ms] in which digital input channels are sampled.
Remark
This command only supports pulse times between 5ms and 255ms.
If no time is set, the default value is 100ms.
This command is not supported by our modules with Ethernet interface
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FILTER_VALUE_SET, 5, 0);
// Sets the time interval to 5ms
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FILTER_VALUE_SET, 150, 0);
// Sets the time interval to 150ms
DapiSpecialCommand - DapiSpecialDIFilterValueGet
This command returns the previously defined value of the time interval for sampling the digital input channels in [ms].
Description
This command returns the previously defined value of the time interval for sampling the digital input channels in [ms].
Definition
ULONG DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FILTER_VALUE_GET, 0, 0);
Parameter
handle=This is the handle of an open module
Return value
Time [ms]
Remark
This command is not supported by our modules with Ethernet interface.
Programming example
value = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FILTER_VALUE_GET, 0, 0);
//Returns the time interval for scanning the digital input channels.
DapiSpecialCommand - Dapi_Special_DI_FF_Filter_Value_Set
This command sets a filter [ms] in which time interval the input flip-flops and the input counters are queried.
Description
This command sets a filter [ms] in which time interval the input flip-flops and the input counters are queried.
Definition
void DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FF_FILTER_VALUE_SET, ULONG time_ms, 0);
Parameter
handle=This is the handle of an open module
time_ms=Time interval [ms] in which digital input channels are sampled.
Remark
This command only supports pulse times between 5ms and 255ms.
If no time is set, the default value is 100ms.
This command is not supported by our modules with Ethernet interface.
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FF_FILTER_VALUE_SET, 5, 0);
// Sets the time interval to 5ms
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI,
DAPI_SPECIAL_DI_FF_FILTER_VALUE_SET, 150, 0);
// Sets the time interval to 150ms
DapiSpecialCommand - Dapi_Special_DI_FF_Filter_Value_Get
This command returns the previously defined value of the time interval for sampling the input flip-flops and the input counters in [ms].
Description
This command returns the previously defined value of the time interval for sampling the input flip-flops and the input counters in [ms].
Definition
ULONG DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FF_FILTER_VALUE_GET, 0, 0);
Parameter
handle=This is the handle of an open module
Return value
Time [ms]
Remark
This command is not supported by our modules with Ethernet interface.
Programming example
value = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_DI, DAPI_SPECIAL_DI_FF_FILTER_VALUE_GET, 0, 0);
//Returns the time interval for scanning the digital input channels.
Digital output functions
DapiDOSet1
This command sets a single output.
Description
This command sets a single output.
Definition
void DapiDOSet1(ULONG handle, ULONG ch, ULONG data);
Parameter
handle=This is the handle of an open module
ch=Indicates the number of the output to be set (0 .. )
data=Indicates the data value to be written (0 / 1)
Return value
None
Requirements
The following SW feature bits must be supported by the module:
DAPI_SW_FEATURE_BIT_CFG_DO
The following conditions for the transfer parameters must be met:
maxCh = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, DAPI_SPECIAL_GET_MODULE_CONFIG_PAR_DO, 0, 0);
maxCh > ch
Programming example
// Output 8 is set to 1
DapiDOSet1(handle, 7, 1);
DapiDOSet8
This command sets 8 digital outputs simultaneously.
Description
This command sets 8 digital outputs simultaneously.
Definition
void DapiDOSet8(ULONG handle, ULONG ch, ULONG data);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the output to be written from (0, 8, 16, 24, 32, ..)
data=Indicates the data values to be written
Return value
None
Programming example
// Outputs 9-12 are set to 0
// Outputs 13-16 are set to 1
DapiDOSet8(handle, 8, 0xf0);
DapiDOSet16
This command sets 16 digital outputs simultaneously.
Description
This command sets 16 digital outputs simultaneously.
Definition
void DapiDOSet16(ULONG handle, ULONG ch, ULONG data);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the output to be written from (0, 16, 32, ..)
data=Indicates the data values to be written
Return value
None
Programming example
// Outputs 1-8 are set to 0
// Outputs 9-16 are set to 1
DapiDOSet16(handle, 0, 0xff00);
DapiDOSet32
This command sets 32 digital outputs simultaneously.
Description
This command sets 32 digital outputs simultaneously.
Definition
void DapiDOSet32(ULONG handle, ULONG ch, ULONG data);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the output from which to write (0, 32, 64, ..)
data=Indicates the data values to be written
Return value
None
Programming example
// Write a value to the outputs
data = 0x0000ff00; // Outputs 9-16 are set to 1
DapiDOSet32(handle, 0, data); // Chan Start = 0
printf("Schreibe auf Ausgänge Daten=0x%x\n", data);
printf("Taste für weiter\n");
getch();
// ----------------------------------------------------
// Write a value to the outputs
data = 0x80000000; // Ausgang 32 wird auf 1 gesetzt
DapiDOSet32(handle, 0, data); // Chan Start = 0
printf("Schreibe auf Ausgänge Daten=0x%x\n", data);
printf("Taste für weiter\n");
getch();
// ----------------------------------------------------
// Write a value to the outputs
data = 0x80000000; // Ausgang 64 wird auf 1 gesetzt
DapiDOSet32(handle, 32, data); // Chan Start = 32
printf("Schreibe auf Ausgänge Daten=0x%x\n", data);
printf("Taste für weiter\n");
getch();
DapiDOSet64
This command simultaneously sets 64 digital outputs.
Description
This command sets 64 digital outputs simultaneously.
Definition
void DapiDOSet64(ULONG handle, ULONG ch, ULONGLONG data);
Parameter
handle=This is the handle of an open module
ch=Indicates the number of the output to be written from (0, 64, ..)
data=Indicates the data values to be written
Return value
None
Programming example
// Outputs 1-32 are set to 0
// Outputs 33-64 are set to 1
DapiDOSet64(handle, 0, 0xffffffff00000000);
DapiDOReadback32
This command reads back the 32 digital outputs.
Description
This command reads back the 32 digital outputs.
Definition
ULONG DapiDOReadback32(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the output from which to read back (0, 32, 64, ..)
Return value
Status of 32 outputs.
Programming example
// Read back channel 1-32
unsigned long data;
data = DapiDOReadback32(handle, 0);
DapiDOReadback64
This command reads back the 64 digital outputs.
Description
This command reads back the 64 digital outputs.
Definition
ULONG DapiDOReadback64(ULONG handle, ULONG ch);
Parameter
handle=This is the handle of an open module
ch=Specifies the number of the output from which to read back (0, 32, 64, ..)
Return value
Status of 64 outputs.
Programming example
// Read back channel 1-64
unsigned long data;
data = DapiDOReadback64(handle, 0);
DapiDOSetBit32
This command can be used to switch outputs specifically to 1 without changing the states of the neighboring outputs.
Description
This command can be used to switch outputs specifically to 1 without changing the states of the neighboring outputs.
Definition
void DapiDOSetBit32(uint handle, uint ch, uint data);
Parameter
handle = This is the handle of an open module
ch = Specifies the number of the output from which to write
data = Specifies the data value to be written (up to 32 bits)
Return value
None
Remark
Only the bits with a value of 1 in the data parameter are taken into account by the command.
Programming example
data = 0x1; // Output 0 would be changed to 1. The states of outputs 1-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xf; // Outputs 0-3 would be changed to 1. The states of outputs 4-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xff; // Outputs 0-7 would be changed to 1. The states of outputs 8-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xff000000; // Outputs 23-31 would be changed to 1. The states of outputs 0-21 won't be changed
DapiDOSetBit32(handle, 0, data);
DapiDOClrBit32
This command can be used to switch outputs specifically to 0 without changing the states of the neighboring outputs.
Description
This command can be used to switch outputs specifically to 0 without changing the states of the neighboring outputs.
Definition
void DapiDOClrBit32(uint handle, uint ch, uint data);
Parameter
handle = This is the handle of an open module
ch = Specifies the number of the output from which to write
data = Specifies the data value to be written (up to 32 bits)
Return value
None
Remark
Only the bits with a value of 1 in the data parameter are taken into account by the command.
Programming example
data = 0x1; // Output 0 would be changed to 0. The states of outputs 1-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xf; // Outputs 0-3 would be changed to 0. The states of outputs 4-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xff; // Outputs 0-7 would be changed to 0. The states of outputs 8-31 won't be changed
DapiDOSetBit32(handle, 0, data);
data = 0xff000000; // Outputs 23-31 would be changed to 0. The states of outputs 0-21 won't be changed
DapiDOSetBit32(handle, 0, data);
DapiDOSet1_WithTimer
This function sets a digital output (ch) to a value (data - 0 or 1) for a specific time in ms.
Description
This function sets a digital output (ch) to a value (data - 0 or 1) for a specific time in ms.
Definition
void DapiDOSet1_WithTimer(ULONG handle, ULONG ch, ULONG data, ULONG time_ms);
Parameter
handle=This is the handle of an open module
ch=Indicates the number of the output to be set (0 .. )
data=Indicates the data value to be written (0 / 1)
time_ms=Indicates the time in which the output is set [ms].
Return value
None
Remark
This command is supported by all output modules of the NET series, as well as by our RO-O8-R8 module.
This command loses its validity if it is overwritten with other values.
If you want to deactivate the command, it must be overwritten with time_ms=0.
Programming example
DapiDOSet1_WithTimer(handle, 2, 1, 1000);
//Setting channel 2 for 1000msec to 1
Timeout protection function
DapiSpecialCMDTimeout
This command is used to set the timeout protection function.
Description
This command is used to set the timeout protection function.
There are three different timeout methods since 2021.
"normal" timeout
This is the timeout that our modules have had since 2009.
Procedure for the timeout command:
The timeout is activated by command.
If a so-called timeout event then occurs (pause between two accesses to the module is longer than the permitted timeout time), the following happens:
- All outputs are switched off.
- The timeout status changes to "2".
- The timeout LED goes on (for modules that have such a status)
Further access to the outputs is then still possible, but the timeout is no longer active. Only when it has been reactivated.
"auto reactivate" timeout
This is a timeout mode implemented since 2021, which automatically reactivates the timeout after the timeout event occurs.
Procedure for the timeout command:
The timeout is activated by command.
If a so-called timeout event then occurs (pause between two accesses to the module is greater than the permitted timeout time), the following happens:
- All outputs are switched off.
- The timeout status changes to "4".
- The timeout LED goes on (for modules that have such a status)
Further access to the outputs is then still possible. AND the timeout is still active. If the timeout time is exceeded again, the outputs are switched off again.
"secure outputs" timeout
This is a timeout mode implemented since 2021, which prevents write access to the outputs after the timeout event occurs, thus ensuring that the software must first restore a "secure" state of the outputs, as the module's timeout mechanism has changed the outputs to predefined values.
Procedure for the timeout command:
The timeout is activated by command.
If a so-called timeout event then occurs (pause between two accesses to the module is longer than the permitted timeout time), the following happens:
- All outputs are switched off.
- The timeout status changes to "6".
- The timeout LED goes on (for modules that have such a status)
Further access to the outputs is NOT possible. The outputs can only be written to after the timeout has been reactivated or deactivated.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, par1, par2);
Parameter
handle = This is the handle of an open module
cmd = function to be executed
par1 = value that is passed to the function
par2 = Value that is passed to the function
DapiSpecialTimeoutSetValueSec
This command is used to set the timeout time.
Description
This command is used to set the timeout time.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, par1, par2);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_SET_VALUE_SEC
par1 = seconds [s]
par2 = milliseconds [100ms] (value 6 = 600ms)
Remark
The permissible value range of the time specification is between 0.1 seconds and 6553 seconds
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_SET_VALUE_SEC, 3, 7);
//The timeout time is set to 3.7 sec.
DapiSpecialTimeoutActivate
This command activates the "normal" timeout.
Description
This command activates the "normal" timeout.
After the timeout event...
- ...all outputs are switched off
- ...the timeout status is set to "2"
- ...the timeout LED is switched on (for modules that have such a status)
Further access to the outputs is then still possible, but the timeout is no longer active.
Only when it has been reactivated.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_ACTIVATE
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_ACTIVATE, 0, 0);
//The "normal" timeout is activated.
DapiSpecialTimeoutActivateAutoReactivate
This command activates the "auto reactivate" timeout.
Description
This command activates the "auto reactivate" timeout.
In this mode, the timeout is automatically reactivated after the timeout event.
After the timeout event...
- ...all outputs are switched off
- ..the timeout status is set to "4"
- ...the timeout LED is switched on (for modules that have such a status)
Further access to the outputs is then still possible AND the timeout is still active.
If the timeout time is exceeded again, the outputs are switched off again.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_ACTIVATE_AUTO_REACTIVATE
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_ACTIVATE_AUTO_REACTIVATE, 0, 0);
//The "auto reactivate" timeout is activated.
DapiSpecialTimeoutActivateSecureOutputs
This command activates the "secure outputs" timeout.
Description
This command activates the "secure outputs" timeout.
In this mode, write access to the outputs is prevented after a timeout event.
This ensures that the software must first restore a "secure" state of the outputs,
as the module's timeout mechanism has changed the outputs to predefined values.
After the timeout event...
- ...all outputs are switched off
- ..the timeout status is set to "6"
- ..the timeout LED is switched on (for modules that have such a status)
Further access to the outputs is NOT possible. Only after reactivating the
timeout or deactivating the timeout, the outputs can be written to.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_ACTIVATE_SECURE_OUTPUTS
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_ACTIVATE_SECURE_OUTPUTS, 0, 0);
//The "secure outputs" timeout is activated.
DapiSpecialTimeoutDeactivate
This command deactivates the timeout.
Description
This command deactivates the timeout.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DEACTIVATE
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DEACTIVATE, 0, 0);
//The timeout is deactivated.
DapiSpecialTimeoutGetStatus
This command is used to read out the timeout status.
Description
This command is used to read out the timeout status.
Definition
ULONG DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, DAPI_SPECIAL_TIMEOUT_GET_STATUS, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_GET_STATUS
Return value
Return = 0 (timeout is deactivated)
Values for the "normal" timeout
Return = 1 (timeout "normal" is activated)
Return = 2 (timeout "normal" has taken place)
Values for the "auto reactivate" timeout
Return = 3 ("auto reactivate" timeout is activated)
Return = 4 ("auto reactivate" timeout has occurred once or several times)
Values for the "secure" timeout
Return = 5 ("secure" timeout is activated)
Return = 6 (Timeout "secure" has taken place. Writing to the outputs is prevented in this status)
Programming example
unsigned long status = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_GET_STATUS, 0, 0);
printf("Status = %ul\n", status);
// Query the timeout status with output.
DapiSpecialTimeoutDoValueMaskWRSet32
This command activates relays in the event of a timeout.
Description
This command determines the outputs that are to be set in the event of a timeout.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, ch, par2);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_WR_SET32
ch = Specifies the number of the output from which to write (0, 32, 64, ..)
par2 = [32 Bit] Specifies the outputs which are to be activated in the event of a timeout
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_WR_SET32, 0, 0xff);
//The first 8 relays are switched on in the event of a timeout.
DapiSpecialTimeoutDoValueMaskRDSet32
This command is used to read out the transferred values.
Description
This command is used to read the transferred values
Definition
ULONG DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_RD_SET32
Return value
[32 bit] Value that is transferred to the SET command
Programming example
unsigned long value = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_RD_SET32, 0, 0);
printf("%0x\n", value);
//The value that was transferred to the SET command is read out and displayed.
DapiSpecialTimeoutDoValueMaskWRClr32
This command deactivates relays in the event of a timeout.
Description
This command determines the outputs that are to be switched off in the event of a timeout.
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, ch, par2);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_WR_CLR32
ch = Specifies the number of the output from which to write (0, 32, 64, ..)
par2 = [32 Bit] Specifies the outputs that are to be deactivated in the event of a timeout
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_WR_CLR32, 0, 0xff);
// The first 8 relays are switched off in the event of a timeout.
DapiSpecialTimeoutDoValueMaskRDClr32
This command is used to read out the transferred values.
Description
This command is used to read out the transferred values.
Definition
LONG DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_RD_CLR32
Return value
[32 bit] Value that is transferred to the CLR command
Programming example
unsigned long value = DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DO_VALUE_MASK_RD_CLR32, 0, 0);
printf("%0x\n", value);
//The value that was transferred to the CLR command is read out and displayed.
DapiSpecialTimeoutDoValueLoadDefault
Resets the SET and CLR values to the original value.
Description
Resets the SET and CLR values to the default value.
(SET value = 0, CLR value = FFFFFFFFFF)
Definition
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT, cmd, 0, 0);
Parameter
cmd = DAPI_SPECIAL_TIMEOUT_DO_VALUE_LOAD_DEFAULT
Programming example
DapiSpecialCommand(handle, DAPI_SPECIAL_CMD_TIMEOUT,
DAPI_SPECIAL_TIMEOUT_DO_VALUE_LOAD_DEFAULT, 0, 0);
//SET and CRL values are set to the default value.
Error handling
DapiGetLastError
This function returns the last error recorded.
Description
This function returns the last recorded error. If an error has occurred, it must be cleared with DapiClearLastError(), otherwise every call to DapiGetLastError() will return the "old" error.
If several modules are to be used, the use of DapiGetLastErrorByHandle() is recommended.
Definition
ULONG DapiGetLastError(void);
Parameter
None
Return value
Error code
0=no error. (see delib_error_codes.h)
Programming example
BOOL IsError()
{
unsigned char msg[500];
unsigned long error_code = DapiGetLastError();
if (error_code != DAPI_ERR_NONE)
{
DapiGetLastErrorText((unsigned char*) msg, sizeof(msg));
printf("Error Code = 0x%x * Message = %s\n", error_code, msg);
DapiClearLastError();
return TRUE;
}
return FALSE;
}
DapiGetLastErrorByHandle
This function returns the last error recorded for a specific module using the handle.
Description
This function returns the last error recorded for a specific module using the handle. If an error has occurred, it must be cleared with DapiClearLastErrorByHandle(), otherwise every call to DapiGetLastErrorByHandle() will return the "old" error.
Definition
ULONG DapiGetLastErrorByHandle(ULONG handle);
Parameter
handle=This is the handle of an open module
Return value
Error code
0=no error. (see delib_error_codes.h)
Programming example
BOOL IsError(ULONG handle)
{
unsigned long error_code = DapiGetLastErrorByHandle(handle);
if (error_code != DAPI_ERR_NONE)
{
printf("Error detected on handle 0x%x - Error Code = 0x%x\n", handle, error_code);
DapiClearLastErrorByHandle(handle);
return TRUE;
}
return FALSE;
}
DapiGetLastErrorText
This function reads out the text of the last error recorded.
Description
This function reads out the text of the last recorded error. If an error has occurred, it must be cleared with DapiClearLastError(), otherwise every call to DapiGetLastErrorText() will return the "old" error.
Definition
ULONG DapiGetLastErrorText(unsigned char * msg, unsigned long msg_length);
Parameter
msg = Buffer for the text to be received
msg_length = Length of the text buffer
Programming example
BOOL IsError()
{
unsigned char msg[500];
unsigned long error_code = DapiGetLastError();
if (error_code != DAPI_ERR_NONE)
{
DapiGetLastErrorText((unsigned char*) msg, sizeof(msg));
printf("Error Code = 0x%x * Message = %s\n", error_code, msg);
DapiClearLastError();
return TRUE;
}
return FALSE;
}
DapiClearLastError
This function deletes the last error that was recorded with DapiGetLastError().
Description
This function deletes the last error that was recorded with DapiGetLastError().
Definition
void DapiClearLastError(void);
Parameter
None
Return value
None
Programming example
BOOL IsError()
{
unsigned char msg[500];
unsigned long error_code = DapiGetLastError();
if (error_code != DAPI_ERR_NONE)
{
DapiGetLastErrorText((unsigned char*) msg, sizeof(msg));
printf("Error Code = 0x%x * Message = %s\n", error_code, msg);
DapiClearLastError();
return TRUE;
}
return FALSE;
}
DapiClearLastErrorByHandle
This function deletes the last error of a specific module (handle) that was recorded with DapiGetLastErrorByHandle().
Description
This function deletes the last error of a specific module (handle) that was registered with DapiGetLastErrorByHandle().
Definition
void DapiClearLastErrorByHandle(ULONG handle);
Parameter
handle=This is the handle of an open module.
Return value
None
Programming example
BOOL IsError(ULONG handle)
{
unsigned long error_code = DapiGetLastErrorByHandle(handle);
if (error_code != DAPI_ERR_NONE)
{
printf("Error detected on handle 0x%x - Error Code = 0x%x\n", handle, error_code);
DapiClearLastErrorByHandle(handle);
return TRUE;
}
return FALSE;
}
Test functions
DapiPing
This command checks the connection to an open module.
Description
This command checks the connection to an open module.
Definition
ULONG DapiPing(ULONG handle, ULONG value);
Parameter
handle=This is the handle of an open module
value=Transferred test value, in the value range of 0-255 (8-bit), to the module
Return value
The test value transferred with "value" must be returned here
Web interface
All DEDITEC products with an Ethernet interface have a graphical web interface that allows you to access the module directly. No apps or additional programs are required for operation other than an Internet browser. You can easily log in to the module from any smartphone, PC, or tablet to manage the device, check status values, or switch outputs.
The integrated user menu allows you to assign a password to prevent unauthorized access to the module. You can also configure network settings and run various services.
The following I/O functions are currently accessible via the web interface:
- Digital inputs: Query statuses, read counters
- Digital outputs: Switch outputs on or off
- Analog inputs: Reading voltage and current values
- Analog outputs: Output voltage and current values
General
The board name of the module can be entered here, which can be used to address the module via DHCP.
The IP protection function prevents the IP address from being read.
Network configuration
All network settings for the module can be configured directly in the "Network configuration" menu.
User management
In the "User management" menu, you can set the login details for accessing the web interface.
Using the "Session valid time" entry, you can specify the period of inactivity after which the user should be automatically logged out.
Status / Reboot
In the "Status / Reboot" menu, you can check the currently installed firmware version, reset the module to factory settings, and perform a restart.
Digital Inputs
The image shows a list of the first 16 digital inputs (CH0 ... CH15) of the module. Depending on the module variant, the next 16 inputs can be displayed via a drop-down menu.
The "State" column indicates whether the signal state at the respective input is high (ON) or low (OFF).
The counted pulses can be read via the "Counter Value." The counter reading is reset to 0 after each hard reset.
Digital Outputs
The image shows a list of the first 16 digital outputs (CH0 ... CH15) of the module. Depending on the module variant, the next 16 outputs can be displayed via a drop-down menu.
An on/off button allows the outputs to be switched on or off individually or all together.
The actual switching status of the outputs can be read back via the "Readback" column.
Analog Inputs
The desired operating mode can be set using the “A/D Mode” drop-down menu.
Analog Outputs
The desired D/A mode is selected via a drop-down menu.
The desired current or voltage value is then entered manually in the "Value" field and written to the outputs via the "SET" button.
The "Readback" column shows the current voltage or current output of the D/A converter.
I/O-Control APP for Android™
Features:
- Separate storage of network settings for private and public networks
- Better clarity thanks to configurable I/O names
- Configurable refresh of all I/Os
The following I/Os are supported:
- up to 128 analog inputs (0..10V, 0..5V, +/- 10V, and +/- 5V)
- up to 64 analog outputs (0..10V, 0..5V, +/- 10V, and +/- 5V)
- up to 128 digital inputs and outputs
Network settings
Module configuration
You can also select which I/Os are to be controlled here.
Digital inputs
The digital inputs are polled at an adjustable interval.
Digital outputs
In the digital outputs section, the channels can be switched on or off individually. It is also possible to switch all channels on or off.
Analog inputs
For the analog inputs, you can choose from the measuring ranges 0..10V, 0..5V, +/- 10V, or +/- 5V. The A/D channels are queried automatically at a configurable interval.
Analog outputs
Here you can set analog outputs in the measuring range 0..10V, 0..5V, +/- 10V, or +/- 5V.
Settings
This image shows the settings for analog outputs. Here, each channel can be given a name.
In addition, you can specify here whether and at what intervals the analog outputs are read back.
These settings are available for all I/Os.
Connection example DI:
Connection example relay:
Connection example MOSFET:
Screwless connector system
The customer-side connection wiring of the inputs and outputs is carried out using screwless, pluggable terminal strips. The conductor connection is made using a so-called actuating tool.
A locking and ejecting mechanism facilitates the insertion and removal of the complete terminal strip.
Handling:
Steps 1-5
Step 1
See the scope of delivery for the operating tool.
Step 2
Insert the operating tool firmly into the side opening in the direction of the conductor connection.
Step 3
Now insert the stripped conductor into the open clamp contact.
Step 4
Pull out the operating tool again.
Step 5
Check that the conductor is properly connected. It should now no longer be possible to pull it out easily.
Manual
Manual BS-WEU series
Quickstart - Hardware description - Software description - ICT-Tool
- Safety instructions
- Installing the drivers
- Connecting the power supply
- Connecting to the PC or network
- Connecting the I/O connectors
- Function test
Hardware description
- List of technical data
- Definition of the LEDs
- Functions of switches and buttons
- Pin assignment of the connectors
- Connection examples
Software description
- Control options via the DELIB, protocol level, DELIB CLI, graphical applications
- DELIB Driver Library, DELIB Sample Sources, DELIB for Linux
- Web interface (only for Ethernet modules)
- DELIB API and its functions
ICT-Tool
- Add module on the PC
- Configure module/interface (Ethernet, USB, CAN, serial)
- Setting options for M2M and event control (only for supported modules)
- Test and diagnose module
- Install firmware updates
- Save/load module configurations using a separate file
Software packages ICT-Tool / DELIB driver library
ICT-Tool + DELIB for Windows (64-bit)
For Windows 11/10, Windows 7, Windows 8, Vista, XP and 2000
Software package for the 64-bit version of the ICT-Tool and the DELIB driver library.
The following operating systems are compatible:
64-bit:
- Windows 10/11 x64
- Windows 8 x64
- Windows 7 x64
- Windows Server 2012 x64
- Windows Server 2008 x64
- Windows Vista x64
- Windows XP x64
- Windows Server 2003 x64
- Windows 2000 x64
Supplied software
ICT-Tool x64
- Updating the DEDITEC module-firmware
- Assigning module addresses
- Module-specific settings
- Configuration of CAN modules
- Test and diagnosis of module functions
- Configuration of the watchdog stick
Replaces the following software
- DT-Flasher x64
- DELIB Module Demo x64
- CAN Configuration Utility x64
- DELIB Module Config x64
- DELIB Configuration Utility x64
- Watchdog Configuration Utility x64
DELIB Command Line Interface x64
Enables the execution of DELIB commands in the command line.
ICT-Tool + DELIB for Windows (32-bit)
For Windows 11/10, Windows 7, Windows 8, Vista, XP and 2000
Software package for the 32-bit version of the ICT-Tool and the DELIB driver library.
The following operating systems are compatible:
32-bit:
-
-
- Windows 10/11
- Windows 8
- Windows 7
- Windows Server 2012
- Windows Server 2008
- Windows Vista
- Windows XP
- Windows Server 2003
- Windows 2000
-
Supplied software
ICT-Tool x32
-
-
- Updating the DEDITEC module-firmware
- Assigning module addresses
- Module-specific settings
- Configuration of CAN modules
- Test and diagnosis of module functions
- Configuration of the watchdog stick
-
Replaces the following software
-
-
- DT-Flasher
- DELIB Module Demo
- CAN Configuration Utility
- DELIB Module Config
- DELIB Configuration Utility
- Watchdog Configuration Utility
-
Attention:
With this version of the driver library, only 32-bit applications can be created, which can then be executed on 32- and 64-bit systems.
DELIB driver library for Linux (32/64-bit)
For 32/64-bit Linux distributions from kernel 2.6.x. Version 2.73 from 28.10.2024
DELIB driver library for Linux distributions (32/64-bit) from kernel 2.6.x
This driver package contains the following components
- DELIB USB driver
- DELIB Ethernet driver
- DELIB CLI
DELIB USB driver
Support for the following products:
- NET series (via USB interface)
- RO-USB series
- BS-USB series
- USB mini-sticks
- USB watchdog
- USB-OPTION-8 / USB-RELAY-8
- USB-TTL-32 / USB-TTL-64
Note:
With the standard version of the USB driver, several USB products with different module IDs (e.g. one RO-USB and one USB-OPTOIN-8) can be addressed. No further driver installation is required.
If several USB products with the same module ID (e.g. a USB-OPTOIN-8 and a USB-RELAIS-8) are to be addressed, the Linux FTDI driver must also be installed. You can find the FTDI driver at http://www.ftdichip.com.
DELIB Ethernet driver
Support for the following products:
- NET series (via Ethernet interface)
- RO-ETH series
- RO-ETH/LC series
- BS-ETH series
- ETH-OPTION-8 / ETH-RELAY-8
- ETH-TTL-64
DELIB CLI
With the DELIB CLI (Command Line Interface) for Linux, all commands for digital and analog I/Os can be set directly via the command line
Manual
Manual for ICT-Tool and DELIB
Software Description - ICT-Tool - DELIB API Reference
Software Description
- Control options via DELIB, protocol level, DELIB CLI, graphical applications
- DELIB driver library, DELIB sample sources, DELIB for Linux
- Web interface (only for Ethernet modules)
- DELIB API and its functions
ICT-Tool
- Add module to PC
- Configure module/interface (Ethernet, USB, CAN, Serial)
- Settings for M2M and Event Control (only for supported modules)
- Test and diagnose module
- Install firmware updates
- Save/load module configurations using a separate file
DELIB API Reference
- Directory structure of DELIB
- Management functions
- Error handling
- Manage digital inputs and outputs
- Manage analog inputs and outputs
- Manage software FIFO
- Manage output timeout
- Register read and write commands
Download
Hardware updates (firmware flash file package)
Firmware flash file package for the ICT tool
This package contains the latest firmware files for the following product series:
- STARTER series
- BS series
- RO series
- NET series
- UC series
- CAN-IO-Box
- Development accessories
The firmware flash file package can alternatively be downloaded via the ICT tool.
USB cable A plug to B plug
USB cable for connecting our modules to the control PC.
- Type: USB 2.0, A plug to B plug
- Length: 1,8 m
2-pin plug connector
Enables the power supply to be connected to the DEDITEC module.
- Type: Phoenix Contact® - 1783287
- 100 % mismatch protected
- For all conductor types from 0.2 mm² to 2.5 mm²
16-pin plug connector
Required for connecting inputs and outputs of the DEDITEC module.
- Type: WAGO® 713-1108/037-000
- Plug-in female multipoint connector with locking mechanism
- 100 % mismatch protected
- 1-wire connection for all conductor types up to 1.5 mm²
Actuating tool for Wago connectors
Used to open and close the terminal contacts on the WAGO® connectors.
- Type: WAGO® - 734-231
BS-CAN interface adapter
Is required to expand BS series modules with a CAN interface.
- CAN (galvanically isolated up to 1 kV RMS)
- CAN 2.0 A or CAN 2.0 B
- 1 Mbit/s, 500 Kbit/s, 250 Kbit/s, 125 Kbit/s, 100 Kbit/s, 50 Kbit/s, 20 Kbit/s oder 10 Kbit/s
- Open CAN protocol
- Automatic processing of CAN packets (Auto RX/TX mode)
- Connection via 9-pin D-Sub socket
BS-RS232 interface adapter
Is required to expand BS series modules with a serial interface.
- RS-232 interface with up to 115200 baud rate
- Connection via 9-pin D-Sub socket
Optional input voltage range 5 V ... 15 V
This option reduces the input voltage range of the OPTOIN modules to 5 V to 15 V. 8 channels per ordered quantity are always modified.
- Input voltage range 5 V to 15 V AC / DC
- 8 channels
USB cable A plug to B plug
USB cable for connecting our modules to the control PC.
- Type: USB 2.0, A plug to B plug
- Length: 1,8 m
2-pin plug connector
Enables the power supply to be connected to the DEDITEC module.
- Type: Phoenix Contact® - 1783287
- 100 % mismatch protected
- For all conductor types from 0.2 mm² to 2.5 mm²
16-pin plug connector
Required for connecting inputs and outputs of the DEDITEC module.
- Type: WAGO® 713-1108/037-000
- Plug-in female multipoint connector with locking mechanism
- 100 % mismatch protected
- 1-wire connection for all conductor types up to 1.5 mm²
Actuating tool for Wago connectors
Used to open and close the terminal contacts on the WAGO® connectors.
- Type: WAGO® - 734-231
Strain relief plate for 16 or 18-pin Wago connectors
The strain relief plate is pushed onto the center of the female connector and enables the connected cables or strands to be fixed in place.
- Type: WAGO® - 713-127
- Strain relief for the connection wiring
- Suitable for 16 or 18-pole female connectors
- Slide onto the female connector from the side
Top hat rail
Top-hat rail for mounting our control technology modules.
- DIN rail according to DIN EN 50022
- Type: Phoenix Contact® - 1208131
- Dimensions in mm: 450 x 35 x 7.5 (L x W x H)
24V/2A power supply unit for top-hat rail mounting
The DR-4524 from Mean Well is a 48W power supply unit for DIN rail mounting for industrial applications. It offers protection against short circuit, overload, overvoltage and overheating.
- Input voltage range: 85 V.. 264 V AC / 120 V DC ... 370 V DC
- Output voltage: 24 V DC
- Output current: 2 A
- Rated power: 48 W
12 V top-hat rail relay
PLC interface for limit continuous currents up to 10 A, consisting of basic terminal with screw connection and plug-in miniature relay. Can be mounted on NS 35/7.5 mounting rail.
- Rated voltage: 230 V AC / 220 V DC
- Switching voltage: 250 V AC / DC
- 1 Changer
- Reverse polarity protection, freewheeling diode
- LED for voltage display
- Type: Phoenix Contact® - 2967617, PLC-RSC- 12DC/21HC
24 V top-hat rail relay
PLC interface for limit continuous currents up to 10 A, consisting of basic terminal with screw connection and plug-in miniature relay. Can be mounted on NS 35/7.5 mounting rail.
- Rated voltage: 24 V AC/DC
- Switching voltage: 250 V AC/DC
- 1 Changer
- Reverse polarity protection, freewheeling diode
- LED for voltage display
- Type: Phoenix Contact® - 2967633, PLC-RSC- 24UC/21HC
Typical Application Areas:
- Building Automation and Smart Home:
Networked control of lights, blinds, heating, and other devices for comfortable, automated living. - IoT applications and connected systems:
Real-time control over Ethernet, centralized monitoring, and easy integration into IoT platforms are realized via the BSW-OR8-64. - Process automation and remote control:
Flexible integration into existing networks for remote maintenance, monitoring, and automated processes is easily possible with the module with High-side MOSFET outputs. - Mobile control & service applications:
With a web interface and app access, systems can be conveniently configured, controlled, and maintained via smartphone or tablet—even in the field. - Rapid prototyping of automation solutions:
USB-based systems enable the BSW-OR8-64 to quickly implement and validate new control and automation concepts. - Process optimization through automation:
Thanks to the integrated auto TX/RX mode, modules can communicate directly with each other and exchange signals—without the need for an additional control PC. - Use for connecting decentralized automation modules:
Through the serial interface, remote functional modules can be integrated into existing control architectures and centrally configured. - Inspection and test systems:
Precise load control, repeatable test sequences, and safe switching logic in laboratory and test environments are supported by the module with High-side MOSFET outputs. - Energy and load management:
The module with High-side MOSFET outputs enables targeted switching of loads and energy sources, for example in energy management systems, backup power solutions, or smart distribution networks. - Safety-critical control systems (fail-safe):
The integrated fail-safe and timeout function of the BSW-OR8-64 ensures that defined states are automatically maintained in the event of communication failures—especially important for safety-critical applications.
Comparison of BSW-OR8-64 with common market products
Interfaces & Communication |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
|---|---|---|---|
| Interfaces | Usually only USB or PCI | USB, Ethernet and web interface | Enables flexible connectivity options in various IT and industrial environments. |
| Supported protocols | Usually only TCP | HTTP, UDP, TCP, DHCP, Modbus‑TCP | Expands application possibilities in modern network and IoT infrastructures. |
| Number of USB modules that can be used simultaneously | 1–4 modules, often without proper management | Up to 16 modules per system | Enables larger system configurations without additional distributors or expansion devices. |
| Galvanic isolation of the CAN interface | A galvanically isolated CAN interface is not standard on all devices. | Electrically isolated CAN interface rated up to 500 V for reliable communication in industrial environments. | Improves interference immunity and protects communication in harsh industrial environments. |
Digital inputs |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Counter function per channel | Often only simple status queries or a global counting function. | 16-bit counters per channel with up to 65,535 count cycles. | Enables direct capture of pulses and events without additional hardware. |
| Wide voltage range | Usually only positive voltage levels are allowed. | Positive and negative voltages can be detected | Expands compatibility with various sensor signals and reduces the need for upstream signal conditioning. |
| Input filter | Filter functions are often fixed or can only be configured to a limited extent. | Programmable filter for input state changes and counter functions. | Reduces bounce and improves the reliable detection of actual switching signals. |
| Status display | Channel statuses are often only visible to a limited extent or in aggregate. | LED status indicator per input and output channel for quick visual inspection. | Speeds up diagnostics, commissioning, and troubleshooting directly at the module. |
| Detection of state changes | Signal changes between two readout cycles are sometimes lost in standard modules. | Internal flip-flops detect transitions from low to high and high to low between two readout operations. | Improves event detection for short signal transitions and asynchronous state changes. |
| Signal isolation of the inputs | Sometimes without galvanic isolation or with reduced protection between the field and logic sides. | Electrically isolated optocoupler inputs for safe signal operation | Increases operational reliability when detecting external switching and sensor signals. |
Digital outputs |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Output type | Standard outputs are often grouped together without specifying their relay characteristics in detail. | Relay outputs with normally open (NO) contacts for standard industrial switching applications. | Suitable for reliably switching external loads in typical industrial applications. |
Automation & Diagnostics |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Status monitoring | Partially without visual indicators | LED status indicators per channel for fast diagnostics | Enables rapid on-site status analysis and reduces the effort required for troubleshooting and diagnostics. |
| Remote access | Barely possible | Direct access via web and Modbus‑TCP | Allows for configuration and monitoring without physical presence, thereby supporting efficient maintenance processes. |
| Diagnostic tools | Mostly not available | Extensive diagnostic capabilities integrated in the ICT tool | Simplifies commissioning, troubleshooting, and long-term analysis through centralized, integrated diagnostic functions. |
| Automated control and monitoring | Additional control PC required | Configurable event control enables automated process monitoring without a control PC | Reduces the need for external control logic and enables automated processes directly within the module. |
| Direct communication without a control PC | M2M functionality is rarely supported | M2M functionality enables the autonomous transmission of process data between different modules | Enables autonomous data transfer between modules and reduces dependence on central control computers. |
| High reliability thanks to M2M functionality | A control PC is required | Built-in M2M functionality enables autonomous operation without a PC | Ensures continued operation even in the event of a control PC failure and increases system availability. |
Hardware flexibility |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Supply voltage | Usually fixed (e.g., +24 V) | Flexible +12 V DC … +28 V DC | Facilitates use in various power supply configurations and reduces the need for additional power supplies. |
| Form factor | Larger modules, less space‑efficient | Very compact with high channel count | Reduces space requirements in the control cabinet and enables higher packing densities. |
| Inputs and outputs | Often only digital inputs or outputs | Combination of digital inputs and relay outputs | Enables compact control solutions without additional expansion modules. |
| Channels / modularity | Fixed number of outputs (e.g., 4–16) | Flexible selection: 8, 16, 32 or 64 channels | Allows for needs-based scaling and reduces oversizing. |
Software & Integration |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Software integration | Limited drivers | DELIB library for C, C++, C#, Java, VB | Simplifies development through standardized programming interfaces and reduces the effort required for custom driver adaptations. |
| Integration into IoT ecosystems | Low, only feasible via gateways | Directly usable via Ethernet in IoT clouds / SCADA / edge systems | Enables direct integration into modern cloud, SCADA, and edge systems without additional gateways. |
| Example programs | Barely available or only upon request | Example programs can be downloaded for free | Accelerates implementation and facilitates the transition to project-specific applications. |
| Support for many protocols | Often only one or two protocols offered | HTTP, UDP, TCP, DHCP, Modbus-TCP | Increases compatibility with existing network infrastructures and enables flexible communication concepts. |
| API concept | Many manufacturers have different APIs per series | Unified API for all series | Simplifies maintenance and further development, as all series can be addressed via the same interface. |
| Firmware updates | Often paid or limited | Free for life | Ensures long-term functionality and enables improvements without additional licensing costs. |
| Example code | Fewer languages or restricted examples | Extensive examples for C, C++, C#, Java, VB, LabView | Supports various development environments and facilitates integration into existing software landscapes. |
| Response times | Partially higher latency with standard I/O | Very fast firmware | Improves real-time performance and enables reliable processing of time-critical signals. |
| System integration | Proprietary systems complicate integration | Easy integration into PLCs, PCs, and test benches | Facilitates integration into existing automation and test systems without extensive modifications. |
| Test system integration | Competitors often more expensive or less flexible | Ideal for automotive and test bench applications | Supports reproducible measurement and test procedures and reduces integration effort in complex test bench environments. |
Mechanical & physical properties |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Mounting | Depending on the supplier, different or less standard designs may be used. | Mounting on a 35 x 7.5 mm DIN rail for use in control cabinets and decentralized I/O systems. | Enables quick and standards-compliant integration into existing control cabinets. |
| Housing quality | Many manufacturers use plastic housings, less robust | Aluminum/metal housing | Increases mechanical durability and improves EMC shielding compared to plastic enclosures |
Reliability |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Long-term availability | Typically 3–5 years | 10‑year guaranteed availability | Simplifies long-term plant planning and reduces risks associated with early product discontinuations. |
| Firmware updates | Often paid or limited | Free for life | Ensures continuous functional improvement without additional operating costs. |
| ICT tool | Often multiple tools, fewer functions | One tool for commissioning, diagnostics, loopback testing, long‑term simulation | Simplifies commissioning, diagnostics, and testing procedures through a centralized software solution. |
| Production location | Many manufacturers produce in Asia | Made in Germany | Enables short supply chains, consistent quality assurance, and a reliable supply of spare parts. |
| Modbus upgrade free of charge | Often paid or not available at all | Yes | Expands communication capabilities without additional licensing costs or hardware changes. |
| MTBF | Low-cost OEM modules with shorter lifespan | High MTBF values | Reduces the probability of failure and increases availability in continuous-operation applications. |
| Failure rate | Higher failure rates with low‑cost I/O | Very low field failure rates | Minimizes unplanned downtime and reduces maintenance and service costs. |
| Spare parts availability | Often early discontinuation | Long‑term spare parts availability | Facilitates maintenance and modernization of existing systems over many years. |
Service and support |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Support quality | Call centers or external service providers | Direct developer support | Enables fast and technically sound problem-solving without the need to escalate issues through external service providers. |
| Response time | Sometimes several days | Very fast response, often same day | Reduces downtime and speeds up the restoration of system operations when technical issues arise. |
| Customization | Rare or very expensive | Custom hardware/firmware possible | Enables project-specific solutions without the need for time-consuming in-house development or additional hardware components. |
| Documentation | Often minimal or incomplete | Comprehensive and practical documentation | Simplifies commissioning and reduces the need for follow-up inquiries thanks to clearly structured and comprehensive technical documentation. |
| Consulting | Often only sales support | Technicians instead of general sales staff | Ensures application-oriented support directly tailored to technical requirements. |
Economy |
|||
| Feature | Market Comparison | Advantages of the DEDITEC BSW-OR8-64</th > | Practical Benefits of the High-side MOSFET outputs modules |
| Price-performance ratio | Major brands significantly more expensive | Very good price‑performance ratio | Reduces total cost per channel and enables cost-effective system expansions. |
| License costs | Modbus/features often require additional payment | No additional costs for protocols | Simplifies cost planning and prevents unexpected follow-up costs associated with functional or protocol expansions. |
| Series prices | Large manufacturers often inflexible | Attractive volume pricing | Simplifies budget planning for larger volumes and enables cost-effective scaling of projects. |
You might also like …
-
USB hybrid digital I/O (DIO/EA) module * USB module with 8 optocoupler inputs and 8 digital outputs
Price range: € 365,33 through € 367,71 Incl. 19% VAT plus shipping View Product -
TCP DI/DO * Ethernet/USB module with 8/16/32/64 * inputs and 8/16/32/64 * outputs (Modbus TCP-compatible)
Price range: € 523,01 through € 1.836,77 Incl. 19% VAT plus shipping View Product -
NET-DEV module with 8 optocoupler inputs and 8 outputs
Price range: € 304,05 through € 327,85 Incl. 19% VAT plus shipping View Product
You might also like …
-
NET-DEV module with 8 optocoupler inputs and 8 outputs
Price range: € 304,05 through € 327,85 Incl. 19% VAT plus shipping View Product -
USB hybrid digital I/O (DIO/EA) module * USB module with 8 optocoupler inputs and 8 digital outputs
Price range: € 365,33 through € 367,71 Incl. 19% VAT plus shipping View Product
Install the installation program and check the module functions.