RO-SER RS-232/RS-485 – Analog input modules with 16/32/64/128 A/D inputs in 16 bit (galvanically isolated)
Price range: € 1.022,81 through € 6.370,67 Incl. 19% VAT plus shipping
Our promise to you
The RO-SER-AD16-128_ISO module is available in versions with 16/32/64/128 analog inputs. The serial standards RS-232 or RS-485 are available as interfaces. In addition, the existing USB 2.0 connection can also be used.
- RS-232/RS-485 interface with galvanic isolation
- Open RS-232/485 protocol, plaintext mode
- USB 2.0 interface with up to 480 Mbit
- 16/32/64/128 A/D inputs with 16-bit resolution each
- Voltage ranges: 0-5V, 0-10V, ±5V, ±10V (optionally available: 0-20V, 0-40V, ±20V, ±40V)
- Current ranges: 0-50mA (optionally available)
- Inputs galvanically isolated up to 500V
- General
- Technical data
- ICT-Tool
- Configuration serial
- Controlling serial
- Connection examples
- Connectors
- Downloads & manuals
- Scope of delivery
- Accessories
Analog inputs
Analog/digital converter modules are suitable for measuring and monitoring voltages and currents. Transducers, for example, convert physical variables such as pressure, temperature, humidity etc. into corresponding currents or voltages and can therefore be recorded and digitally processed with our A/D modules.
A/D filter
Electrical or electromagnetic interference in measurement signals is smoothed and optimized by the software A/D filter by averaging the measurements.
Plug connector
A screwless system from the manufacturer WAGO® Kontakttechnik is used as the connector. The 1-wire female connectors are 100 % protected against mismating and have an ejection and locking mechanism.
LEDs
Each digital input and output has a separate LED that lights up when the signal status is active. The status of the operating voltage, communication with the interface, error events or the occurrence of a timeout can also be displayed.
Software and control for programmers
Our supplied DELIB driver library makes it easy to address the product via our API in almost all programming languages under Windows and Linux.
We offer support for the following programming languages:
- C
- C++
- C#
- VB
- VBA
- VB.Net
- Java
Command-Line-Interface
With the help of the command line interface, or CLI for short, our products with Ethernet or USB interface can be easily addressed via the command line. Our digital and analog inputs/outputs are supported. The CLI is available for Windows and Linux operating systems.
| Power supply | + 12 V ... +24 V DC |
|---|---|
| General LEDs |
|
| LEDs product-specific |
A/D-version:
D/A-version:
CNT version:
Incremental encoder version:
PT100 version:
|
| DIP switch (only for RO-CPU-CAN) |
|
| Mounting type | Can be mounted on 35 x 7.5 mm top-hat rail |
| Operating temperature | +10 °C ... +50 °C |
| Dimensions with 16 I/Os | 122mm x 85 mm x 51,5 mm (H x B x T) |
| Dimensions with 32 I/Os | 122mm x 126 mm x 51,5 mm (H x B x T) |
| Dimensions with 64 I/Os | 122mm x 208 mm x 51,5 mm (H x B x T) |
| Dimensions with 128 I/Os | 122mm x 372 mm x 51,5 mm (H x B x T) |
Interfaces
USB Interface
| USB-Interface |
|
|---|
RS-232 Interface
| RS-232 Interface |
|
|---|
Inputs/Outputs
Analog inputs
| Inputs |
* is not supported by modules of the BS-WEU series |
|---|---|
| Conversion rates |
|
| Galvanic isolation | For power supply: max. 500 V |
| A/D-Filter |
|
Connectors
| Plug connector 18-pin |
|
|---|
The ICT-Tool
Integration, configuration and testing - Our all-in-one Windows tool contains all the functions you need to put our products into operation quickly, easily and efficiently. Start with the setup and configuration, install firmware updates and use the extensive test and diagnostic options. The integrated help menu provides additional support if required.
Below you will find a brief overview of the program’s basic menus.
Module selection
Here you can integrate a new product into the ICT tool by clicking on the “+” symbol and then configure it.
ICT TreeView
In the TreeView, on the left-hand side of the program window, you can see the respective control elements or functions that are supported by your selected module. The scope of the functions depends on the respective product.
Overview
All relevant module information can be accessed here at a glance.
- Module name
- Module ID
- Firmware revision
- MAC address
- LAN and WiFi Network address (module dependent)
Inputs / Outputs
This overview shows the number of I/Os supported by your module.
Module infos
Here you will find all the important feature information for your module.
General features
Here you will find all the important feature information for your module.
Digital I/O features
Here you will find information about the digital I/Os supported by the module.
Analog I/O features
Here you will find information about the type of analog I/Os supported by your module.
Special I/O features
Here you will find information about the type of special I/Os supported by your module.
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
Info
All relevant module information can be called up here at a glance.
- Module name
- Module ID
- Firmware revision
- Interface type
- Current DIP switch setting (only for Ethernet modules)
Identification
If several DEDITEC Ethernet modules are active in the network, a signal LED on the selected module can be activated via an identification function. This facilitates visual assignment.
Restart
You can restart your module here. The module status shows whether the restart was successful.
USB configuration
If you want to use several USB modules from the same product series on one PC, each of these modules must first be assigned its own module number.
LAN info
On this information page, you will find the current LAN network information and all the settings for your module at a glance.
LAN configuration
Integrate the product into your network or control it directly via a 1-to-1 connection.
The following parameters can be changed.
- Board name
- DHCP on/off
- IP address
- Subnet mask
- Default gateway
- TCP Port
WiFi info
All important WiFi settings are displayed on this page
WiFi configuration
Here you can change the network settings of the selected WiFi product.
The following settings can be made:
- Board name
- WLAN on/off
- Router name
- Router password
WPS
With the WPS function, your module can be connected to the router quickly and easily, automatically (WPS on the router is required)
CAN configuration
With our CAN products in the BS, NET and UC series, settings for the interface and the TX/RX packets can be made using the ICT tool.
More information can be found here:
Serial configuration
For our serial products in the BS, NET, UC and RO series, changes to the interface can be made using the
ICT tool.
More information can be found here:
Modbus TCP
Here you can set the Modbus TCP configuration of the module.
The following configurations can be made.
- Enable/disable access via Modbus TCP
- TCP port
TCP encryption
Here you can make settings for the encryption of your module.
The following configurations can be made.
- Allow unencrypted protocol
- Allow “User” encryption mode
- User password
- Allow “Admin” encryption mode
- Admin password
NTP configuration
You can make changes to the NTP service here.
The following configurations can be made.
- NTP service on/off
- server
- Port
- Timezone
WEB-Login
Here you can change the login settings of the web interface.
The following configurations can be made.
- Session duration
- Login name
- Login password
- Allow I/O access via web interface
D/A Default Values
Here you can set the D/A values and modes with which the module should be started.
The value and mode can be set individually for each channel.
Watchdog configuration
Here you can make and save settings on your watchdog stick.
Save or Load config
Using the “Save or Load config” function, you can save your entire module configuration in an external XML file.
This means you can always load your module in the desired original state.
The following configurations can be saved depending on the module type.
- USB configuration
- LAN configuration
- WiFi configuration
- TCP encryption
- NTP configuration
- Serial configuration
- CAN configuration
Status
This gives you an overview of the activity of the transmitter and receiver module
The following information from the transmitter module is displayed:
- Status of the activity: If the check mark is set, this action is currently being performed.
- Total number of actions performed. Is reset to 0 after a restart of the module.
- Number of actions per second.
- Number of DELIB errors that occur when executing commands from the DEDITEC driver library.
The following information from the receiver module is displayed:
- Connected: If the check mark is set, the transmitter and receiver modules are connected.
- IP address of the receiver module.
- Number of connection attempts.
Receiver modules
You can set the network settings of the receiver module here.
The following settings can be made
- Name for the receiver module
- Network settings of the receiver module
- Timeout
- Encryption type/ password
Action
With an action, you define which input signal is to be sent from the transmitter module to which output of a receiver module.
The following settings can be made:
- Type of task (digital, analog)
- Which receiver module should be used
- The interval at which the operations are to be carried out
- Start channel of the transmitter module
- Number of channels to be transmitted
- Start channel of the receive module
In the image on the right, DI data is sent every 100ms from channel 3(CH Start) to channel 8 ((CH Start) + (CH Count)) to channels 0-5 of the target module.
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
Status
The Status area provides an overview of all active events and executed actions.
The following information is listed:
- Event number
- Event type
- Time interval of the event
- Number of events that have occurred
- Action number
- Number of triggered actions
- Number of other actions
Events configuration
Up to 16 different events can be created in the configuration menu. An event can be used, for example, to define switching thresholds at the analog inputs or logical states at the digital inputs of the module and link them to an executable action. The configuration itself is saved permanently in the module configuration memory of the module.
The following event modes are available, depending on the module type:
- DI: High-Low state of a digital input.
- DI flip-flop: Status change of a digital input (is stored in the module with the so-called flip-flop flag and deleted again after readout).
- DO readback: ON-OFF status of a digital output (is read out using a DO readback command).
- A/D: Current or voltage level at the analog inputs
Configuration actions
Up to 16 different actions can be created in the configuration menu. An action defines what should happen within an event after a condition is met.
The following action modes are available, depending on the module type:
- Set DO output: Switches a digital output on or off
- Set D/A output: Outputs a current or voltage value at an analog output
- Send CAN packet: A special CAN TX event is triggered (up to eight CAN TX events can be configured separately).
Digital Out
Hier können Sie die digitalen Ausgänge Ihres Modules ein- und ausschalten.
Folgende Funktionen können in dieser Form getestet werden.
- Kanalweise Ein- und Ausschalten der digitalen Ausgänge
- Readback der Kanäle
- Setzen eines Digitalausgangs für eine bestimmte Zeit (Modulabhängig)
- Gibt an welchen Status die Kanäle nach Ablauf der Zeit einnehmen sollen (Modulabhängig)
- Testen der Ausgänge
Digital Out
All digital outputs of your product can be checked by clicking on the buttons.
The following switching options are possible:
- Switching on and off channel by channel
- Channel-by-channel switching on or off for a specific time (product-dependent)
- Reading back the switching status (readback)
Digital In
In this view, the logical states of all optocoupler inputs can be read out.
The following information is displayed:
- Logical status of the inputs (ON/OFF)
- Number of detected pulses (counter function)
- Change of state detected (flip-flop)
TTL I/O
In this menu, the TTL channels of the module can be configured as inputs or outputs. The individual TTL outputs can be switched on or off by pressing the buttons. In addition, the status of all TTL inputs can be read out.
The tool offers the following functions:
- Configuration of the channels as input or output (in blocks of 8)
- Switching on and off channel by channel
- Reading back the switching status (output readback)
- Displaying the logical status of the inputs (input readback)
Analog Out
Here you can test the analog outputs of the module and manually enter any voltage or current value.
Analog In
In this menu, voltage or current values of all A/D channels can be displayed.
It is also possible to activate our A/D software filter with different filter levels.
CAN Runtime Parameter
Here you can change the CAN settings of the interface, the RX and TX packets in runtime.
The following settings can be made:
- Baud rate
- Extended ID
- Active on/off
- CAN ID
- Mode
CNT48
Here you can read out the counter readings of a counter module, select filter options and set various counting modes.
The following counting modes are supported:
- Read on rising edge
- Read on rising edge x2
- Read on rising edge x4
- Period duration
- Frequency measurement
- PWM measurement
Pulse generator
The pulse generator can be used to generate square-wave signals. High and low time as well as the number of pulses can be set here.
PWM Out
In this menu you have the option of testing various PWM frequencies. In addition, the duty cycle can be entered manually for each individual channel.
Temp
The temperature of all connected temperature sensors is displayed here directly in °C.
Graphical display
This menu allows a graphical representation of all analog input signals, such as A/D, temperature or FIFO-IN.
Watchdog
This tool can be used to check the configured watchdog parameters for correct function.
I/O – Timeout
You can use the timeout function in the I/O area to simulate a timeout case for your module.
The following is a description of the timeout window
- Read / Write symbol: Flashes to indicate an active connection to the module
- Automatic access: Removing the tick triggers a timeout after the timeout time has expired
- Manual access: Manual retrieval of data from the module
- Timeout status: Shows whether the timeout is active and whether a timeout event has occurred
- Timeout mode: Selection between 3 timeout modes, Normal, Reactivate and Secure
- Timeout duration: The time after which the timeout should be triggered is set here
- Activate / deactivate: Activates or deactivates the timeout function
Access times tests
You can test the access times for the module here. The following access time tests can be performed:
- Register – Read/Write/Write + Readback
- Digital I/O – Read/Write/Write + Readback
- Analog I/O – Read/Write/Write + Readback
Access times tests
This test can be used to determine the access times to the module. The test values are read and written in 8, 16, 32, or 64-bit commands.
Access times Register
The following example checks the register accesses to an Ethernet module. The average access time here is 0.5 ms.
Access times Analog I/O
In the following example, the access times to an Ethernet module with analog I/Os are checked. The average access time here is 0.6 ms.
Access times Digital I/O
In the following example, the access times to an Ethernet module with digital I/Os are checked. The average access time here is 0.6 ms.
Cable feedback tests
For this test, the digital or analog outputs of the module are connected to the corresponding digital or analog inputs of the module via cable. The feedback test now checks whether the output and input values match.
Cable return test
The cable return test can be used to check the function of all digital and analog inputs and outputs (I/Os) of a module. To do this, inputs and outputs are wired together externally on a 1:1 basis. The test software analyzes whether the output signals arrive correctly at the inputs, thereby identifying wiring errors or hardware defects.
Analog test
In analog test mode, the D/A converter outputs defined test voltages, which are then read in by the A/D converter and compared with the target values. The software counts the number of test runs and automatically documents any deviations.
Digital test
In the digital test, the switching states of the relay or MOSFET outputs are fed back externally to the optocoupler inputs. Here, too, the software counts and compares the number of cycles and automatically detects transmission errors or deviations.
Cable return test
The cable return test can be used to check the function of all digital and analog inputs and outputs (I/Os) of a module. To do this, inputs and outputs are wired together externally on a 1:1 basis. The test software analyzes whether the output signals arrive correctly at the inputs, thereby identifying wiring errors or hardware defects.
Analog test
In analog test mode, the D/A converter outputs defined test voltages, which are then read in by the A/D converter and compared with the target values. The software counts the number of test runs and automatically documents any deviations.
Digital test
In the digital test, the switching states of the relay or MOSFET outputs are fed back externally to the optocoupler inputs. Here, too, the software counts and compares the number of cycles and automatically detects transmission errors or deviations.
A/D ripple
The ripple test displays the residual ripple of the individual A/D inputs.
A/D quality measurements
The quality of an A/D measurement is influenced by various factors and can be affected by external interference. A reliable method for checking measurement quality is to measure a stable battery voltage. Our diagnostic tools can be used to determine the residual ripple and noise behavior.
A/D ripple
The A/D ripple test can be used to measure the residual ripple of the individual A/D inputs and check for interference signals such as mains hum or voltage instabilities.
A/D noise
The noise behavior of each A/D channel can be displayed graphically using A/D noise measurement. Additional filter stages with averaging can be used to smooth and improve the measurement signal.
FIFO In/Out
The software FIFO test can be used to specifically test the integrated FIFO buffering of our digital and analog NET I/O modules. Depending on whether it is an input or output module, data is read from the submodule FIFO or written to the submodule FIFO.
FIFO settings
The submodule number can be used to specify which module is to be tested. The start and end channels can also be used to transmit several channels simultaneously. In addition, the transmission frequency can be set and the desired FIFO mode selected – for example, for the use of test values or the actual measured values of the module.
All important information at a glance
During program execution, key information such as the size of the data packets, free and occupied bytes in the FIFO buffer, the number of data packets sent or received, and the current FIFO status are clearly displayed.
D/A output test
The D/A output test enables targeted testing of each individual D/A channel of a module. A freely selectable test voltage can be output directly. Currently, simple square wave signals with configurable high and low times are available. The signals can be monitored simultaneously with an oscilloscope. This function is also ideal for long-term tests. The test software detects DELIB errors and logs them automatically.
Mustertext
Mustertext
DO 4* value + wait
In this test, adjustable 16-bit values are written to the digital outputs of the module.
The values are sent to the module using the DapiDOSet16 command. The start channel is always channel 0.
You can set different wait times between the individual calls.
The test is intended for testing the functionality of the module.
Mustertext
Mustertext
Modbus I/O test
In the diagnostics section of the ICT-Tool, you can test the module’s digital and analog inputs and outputs directly via Modbus TCP. Register addresses as well as transfer and return values are displayed in a debug panel, allowing you to quickly diagnose problems with the D/A converter, for example. A complete overview of all register addresses and examples can be found in the Modbus manual at the following link:
To benefit from the latest functions and prevent errors, we recommend that you always keep your DEDITEC product up to date.
Flash Files
Downloading the firmware flash file package via the ICT tool
- Go to Flash Files in the “Firmware update” menu
- Click on the download button to start the download.
- Administration rights are required for the automatic unpacking of the flash files. If these rights are not available, the files are downloaded to the download area of your PC and must be extracted manually to the installation directory.
\DEDITEC\DELIB\programs\flash_files
Downloading the firmware flash file package via the DEDITEC homepage
- Download the required firmware flash file package from our homepage: Downloads -> Software -> Firmware
- Extract the files to the following installation path: ..\DEDITEC\DELIB\programs\flash_files
Flash modules
In the “Firmware update” menu, select the module you want to update and then click on the “Flash modules” or “Flash submodules” button.
The firmware is now updated and the module is then restarted automatically.
Information on the firmware flasher
The following information is displayed in the firmware flasher:
- Last FW: Displays the last firmware version
- Current FW: Displays the currently installed firmware version
- Newest FW: Displays the latest firmware version
- Log: Displays status or error messages during the flash process
In den folgenden Kapitel, würden wir Ihnen unsere neue All-In-One-Software gerne genauer vorstellen.
General
Here you can make general configurations to the ICT tool.
The following changes can be made:
- Language – setting between German and English possible
Updates
Here you can search for available DELIB or firmware updates.
- Automatic update search at program start
- Search for DELIB updates
- Search for firmware updates
Error log
Here you can make settings for the deditec_debug.log. This is saved under the path C:\Users\?USER?\AppData\Local\DEDITEC.
The following settings can be made:
- Enable writing to the debug.log
- Activate log notifications
- Activate automatic deletion of the debug.log
- Setting after how many days the debug.log should be deleted
- Set the maximum size of the debug.log
DELIB – DebugView – Global
Settings can be made here for the information that is to be displayed with the DebugView.
- Activate debug output
- Activate display of errors
DELIB – DebugView – Details
More detailed settings can be made here for the information to be displayed with the DebugView.
Configuration of our serial modules (RS-232 / RS-485)
To configure the serial interface, the module must be connected to the PC either via the Ethernet interface or USB interface.
The module can then be accessed and configured in the ICT tool.
The following parameters can be set:
- Preferred mode (115k baud, module address = deactivated, echo = off)
- Baud rate
- Module address (only for RS-485)
- Echo active on/off
- Text mode / Register mode
Changing the interface standard
Switch between RS-232 and RS-485 (applies only to NET and RO series)
The modules are configured for RS-232 operation as standard when delivered. The module can be switched to RS-485 operation by changing the jumper positions. Further information on this can be found in the manual for the respective product.
Control of our RS-232 / RS-485 modules
There are two options available for controlling our RS-232 / RS-485 modules:
1. Register-based via an open protocol
2. Via plain text input via a terminal program
Please note!
We only recommend using the RS-485 interface in conjunction with a microcontroller and your own serial protocol.
1. Control via our open serial protocol
Serial control is register-based. An open communication protocol was created for this purpose, which is used to address the module's registers and thus execute read or write commands. The “Protocols & Register Assignment” manual describes the transmission and reception frames for communicating with RS-232/RS-485 modules.
2. Control via plain text using HyperTerminal
The digital inputs and outputs can be controlled or read directly via “plain text” using HyperTerminal. Examples of this can be seen in the adjacent illustration.
Connection example AD16:
Screwless connector system
The customer-side connection wiring of the inputs and outputs is carried out using screwless, pluggable terminal strips. The conductor connection is made using a so-called actuating tool.
A locking and ejecting mechanism facilitates the insertion and removal of the complete terminal strip.
Handling:
Steps 1-5
Step 1
See the scope of delivery for the operating tool.
Step 2
Insert the operating tool firmly into the side opening in the direction of the conductor connection.
Step 3
Now insert the stripped conductor into the open clamp contact.
Step 4
Pull out the operating tool again.
Step 5
Check that the conductor is properly connected. It should now no longer be possible to pull it out easily.
Manual
Manual RO series
Quickstart - Hardware description - Software description - ICT tool
Commissioning/Quickstart
- Safety instructions
- Installing the drivers
- Connecting the power supply
- Connecting to the PC or network
- Connecting the I/O connectors
- Function test
Hardware description
- List of technical data
- Definition of the LEDs
- Functions of switches and buttons
- Pin assignment of the connectors
- Connection examples
Software description
- Control options via the DELIB, protocol level, DELIB CLI, graphical applications
- DELIB driver library, DELIB sample sources, DELIB for Linux
- Web interface (only for Ethernet modules)
- DELIB API and its functions
ICT-Tool
- Add module to PC
- Configure module / interface (Ethernet, USB, CAN, serial)
- Setting options for M2M and event control (only for supported modules)
- Test and diagnose module
- Install firmware updates
- Save / load module configurations using a separate file
Software packages ICT-Tool / DELIB driver library
ICT-Tool + DELIB for Windows (64-bit)
For Windows 11/10, Windows 7, Windows 8, Vista, XP and 2000
Software package for the 64-bit version of the ICT-Tool and the DELIB driver library.
The following operating systems are compatible:
64-bit:
- Windows 10/11 x64
- Windows 8 x64
- Windows 7 x64
- Windows Server 2012 x64
- Windows Server 2008 x64
- Windows Vista x64
- Windows XP x64
- Windows Server 2003 x64
- Windows 2000 x64
Supplied software
ICT-Tool x64
- Updating the DEDITEC module-firmware
- Assigning module addresses
- Module-specific settings
- Configuration of CAN modules
- Test and diagnosis of module functions
- Configuration of the watchdog stick
Replaces the following software
- DT-Flasher x64
- DELIB Module Demo x64
- CAN Configuration Utility x64
- DELIB Module Config x64
- DELIB Configuration Utility x64
- Watchdog Configuration Utility x64
DELIB Command Line Interface x64
Enables the execution of DELIB commands in the command line.
ICT-Tool + DELIB for Windows (32-bit)
For Windows 11/10, Windows 7, Windows 8, Vista, XP and 2000
Software package for the 32-bit version of the ICT-Tool and the DELIB driver library.
The following operating systems are compatible:
32-bit:
-
-
- Windows 10/11
- Windows 8
- Windows 7
- Windows Server 2012
- Windows Server 2008
- Windows Vista
- Windows XP
- Windows Server 2003
- Windows 2000
-
Supplied software
ICT-Tool x32
-
-
- Updating the DEDITEC module-firmware
- Assigning module addresses
- Module-specific settings
- Configuration of CAN modules
- Test and diagnosis of module functions
- Configuration of the watchdog stick
-
Replaces the following software
-
-
- DT-Flasher
- DELIB Module Demo
- CAN Configuration Utility
- DELIB Module Config
- DELIB Configuration Utility
- Watchdog Configuration Utility
-
Attention:
With this version of the driver library, only 32-bit applications can be created, which can then be executed on 32- and 64-bit systems.
DELIB driver library for Linux (32/64-bit)
For 32/64-bit Linux distributions from kernel 2.6.x. Version 2.73 from 28.10.2024
DELIB driver library for Linux distributions (32/64-bit) from kernel 2.6.x
This driver package contains the following components
- DELIB USB driver
- DELIB Ethernet driver
- DELIB CLI
DELIB USB driver
Support for the following products:
- NET series (via USB interface)
- RO-USB series
- BS-USB series
- USB mini-sticks
- USB watchdog
- USB-OPTION-8 / USB-RELAY-8
- USB-TTL-32 / USB-TTL-64
Note:
With the standard version of the USB driver, several USB products with different module IDs (e.g. one RO-USB and one USB-OPTOIN-8) can be addressed. No further driver installation is required.
If several USB products with the same module ID (e.g. a USB-OPTOIN-8 and a USB-RELAIS-8) are to be addressed, the Linux FTDI driver must also be installed. You can find the FTDI driver at http://www.ftdichip.com.
DELIB Ethernet driver
Support for the following products:
- NET series (via Ethernet interface)
- RO-ETH series
- RO-ETH/LC series
- BS-ETH series
- ETH-OPTION-8 / ETH-RELAY-8
- ETH-TTL-64
DELIB CLI
With the DELIB CLI (Command Line Interface) for Linux, all commands for digital and analog I/Os can be set directly via the command line
Manual
Manual for ICT-Tool and DELIB
Software Description - ICT-Tool - DELIB API Reference
Software Description
- Control options via DELIB, protocol level, DELIB CLI, graphical applications
- DELIB driver library, DELIB sample sources, DELIB for Linux
- Web interface (only for Ethernet modules)
- DELIB API and its functions
ICT-Tool
- Add module to PC
- Configure module/interface (Ethernet, USB, CAN, Serial)
- Settings for M2M and Event Control (only for supported modules)
- Test and diagnose module
- Install firmware updates
- Save/load module configurations using a separate file
DELIB API Reference
- Directory structure of DELIB
- Management functions
- Error handling
- Manage digital inputs and outputs
- Manage analog inputs and outputs
- Manage software FIFO
- Manage output timeout
- Register read and write commands
Download
Hardware updates (firmware flash file package)
Firmware flash file package for the ICT tool
This package contains the latest firmware files for the following product series:
- STARTER series
- BS series
- RO series
- NET series
- UC series
- CAN-IO-Box
- Development accessories
The firmware flash file package can alternatively be downloaded via the ICT tool.
USB cable A plug to B plug
USB cable for connecting our modules to the control PC.
- Type: USB 2.0, A plug to B plug
- Length: 1,8 m
DSUB-9 data cable
DSUB-9 data cable for connecting our serial modules to the control PC.
- DSUB-9 socket / plug
- Length: 1,8 m
2-pin plug connector
Enables the power supply to be connected to the DEDITEC module.
- Type: Phoenix Contact® - 1783287
- 100 % mismatch protected
- For all conductor types from 0.2 mm² to 2.5 mm²
16-pin plug connector
Required for connecting inputs and outputs of the DEDITEC module.
- Type: WAGO® 713-1108/037-000
- Plug-in female multipoint connector with locking mechanism
- 100 % mismatch protected
- 1-wire connection for all conductor types up to 1.5 mm²
Actuating tool for Wago connectors
Used to open and close the terminal contacts on the WAGO® connectors.
- Type: WAGO® - 734-231
Optional input current range 0 ... 50 mA
This option changes the input range of the RO-AD16_ISO modules to 0 ... 50 mA. 16 channels are always modified per ordered quantity.
- Input current range 0 ... 50 mA
- 16 channels
Optional input voltage range 0 V ... 20 V
This option increases the input voltage range of the RO-AD16_ISO modules to 20 V. 16 channels per ordered quantity are always modified.
- Input voltage range 0 V ... 20 V
- 16 channels
Optional input voltage range 0 V ... 40 V
This option increases the input voltage range of the RO-AD16_ISO modules to 40 V. 16 channels are always modified per ordered quantity.
- Input voltage range 0 V ... 40 V
- 16 channels
USB cable A plug to B plug
USB cable for connecting our modules to the control PC.
- Type: USB 2.0, A plug to B plug
- Length: 1,8 m
DSUB-9 data cable
DSUB-9 data cable for connecting our serial modules to the control PC.
- DSUB-9 socket / plug
- Length: 1,8 m
2-pin plug connector
Enables the power supply to be connected to the DEDITEC module.
- Type: Phoenix Contact® - 1783287
- 100 % mismatch protected
- For all conductor types from 0.2 mm² to 2.5 mm²
18-pin plug connector
Required for connecting inputs and outputs of the DEDITEC module.
- Type: WAGO® - 713-1109/037-000
- Plug-in female multipoint connector with locking mechanism
- 100 % mismatch protected
- 1-wire connection for all conductor types up to 1.5 mm²
Actuating tool for Wago connectors
Used to open and close the terminal contacts on the WAGO® connectors.
- Type: WAGO® - 734-231
Strain relief plate for 16 or 18-pin Wago connectors
The strain relief plate is pushed onto the center of the female connector and enables the connected cables or strands to be fixed in place.
- Type: WAGO® - 713-127
- Strain relief for the connection wiring
- Suitable for 16 or 18-pole female connectors
- Slide onto the female connector from the side
Top hat rail
Top-hat rail for mounting our control technology modules.
- DIN rail according to DIN EN 50022
- Type: Phoenix Contact® - 1208131
- Dimensions in mm: 450 x 35 x 7.5 (L x W x H)
24V/2A power supply unit for top-hat rail mounting
The DR-4524 from Mean Well is a 48W power supply unit for DIN rail mounting for industrial applications. It offers protection against short circuit, overload, overvoltage and overheating.
- Input voltage range: 85 V.. 264 V AC / 120 V DC ... 370 V DC
- Output voltage: 24 V DC
- Output current: 2 A
- Rated power: 48 W
You might also like …
-
RO-Ethernet/USB-16/32/64/128*A/D inputs Module with galvanically isolated A/D inputs (16 bit) (Modbus TCP-compatible)
Price range: € 999,01 through € 6.358,77 Incl. 19% VAT plus shipping View Product -
RO-CAN-16/32/64/128 * A/D input module with galvanically isolated A/D inputs (16 bit)
Price range: € 1.022,81 through € 6.370,67 Incl. 19% VAT plus shipping View Product -
NET-DEV 16/18-bit A/D converter with galvanic isolation – 2 channels
Price range: € 770,53 through € 973,42 Incl. 19% VAT plus shipping View Product
You might also like …
-
RO-CAN-16/32/64/128 * A/D input module with galvanically isolated A/D inputs (16 bit)
Price range: € 1.022,81 through € 6.370,67 Incl. 19% VAT plus shipping View Product -
NET-DEV 16/18-bit A/D converter with galvanic isolation – 2 channels
Price range: € 770,53 through € 973,42 Incl. 19% VAT plus shipping View Product
Install the installation program and check the module functions.































Reviews