The RO-CAN-O16-64-R16-64 module is available in versions with 16, 32 or 64 inputs and outputs. AC optocouplers are used for the digital inputs, while reed relays were used for the digital outputs. It has a CAN interface with an open CAN protocol and can, with the help of our automatic RX/TX mode, independently receive or send CAN packets within a network.
- CAN interface with galvanic isolation
- Open CAN protocol
- Automatic send/receive mode
- 16/32/64 Digital inputs: 15V – 30V AC/DC (optional 5V – 15V)
- 16/32/64 relay outputs: 1A
- 16 bit counter per input channel (up to 100Hz)
- LED status display per input and output channel
- Timeout protection function
Digital inputs
With our optocoupler inputs, digital signal states can be recorded within a voltage range of 5V to 30V AC or DC. Input and output circuits are galvanically isolated from each other up to 2.5kV.
Digital In Input Filter
With our Digital-In modules, an input filter can be set in a time interval of 1ms…255ms to filter interference pulses.
This means that AC signals can also be detected cleanly.
Counter
Each input has a 16 bit counter that can count up to 65535 pulses. If the maximum counter value is exceeded, the counting process starts again from zero. By means of a software command, the current status of all input counters can be read from the module simultaneously.
Recording of status changes
Status changes that occur between the readout cycles are reliably detected by internal flip-flops and can be read out separately by software. In addition, such an event is signalled by a status LED. Resetting is done automatically after the flip-flops have been read out.
Relais 1A
With the option “Relay outputs (1A)” reed relays with normally open (NO) function are used. They are suitable for smaller switching capacities of up to 1A and have a service life of well over 100 million switching cycles. The electrical isolation between input and output circuit is up to 1.5kV.
Timeout-Protection-Function
If communication with the DEDITEC module is interrupted in a timeout case, the timeout protection function takes effect. It can be set for each digital output whether it is to be “switched off”, “switched on” or left unchanged. Motors can thus be switched off in a timeout case, for example, and connected horns or other alarm transmitters can be switched on.
New timeout modes
3 different timeout modes: “normal”, “auto reactive” and “secure outputs” for different procedures in case of a timeout event.
In “secure outputs” timeout mode, access to the outputs is blocked after a timeout event, thus preventing further access to the outputs.
Unlocking must be done by an additional software command.
Automatic send and receive mode
Use our Auto RX/TX mode and automate the workflow of your DEDITEC product by independently processing or sending CAN packets from or to other participants in the network. With our free tool “CAN Configuration Utility” you can define via a graphical user interface how the RX and TX packets should be processed. For example, you can read the values of an A/D converter and send them to a CAN module with D/A output.
Different configuration modes
The RO-CAN interface can be configured in three different ways and is selected via DIP switches:
The preferred mode with preset CAN default values, a DIP switch mode where all CAN specifications can be set via DIP switches or a software mode where the setup can be easily defined via our CAN Configuration Utility.
LEDs
Each digital input and output has a separate LED that lights up when the signal state is active. Furthermore, the status of the operating voltage, the communication with the interface, error events or the occurrence of a timeout can be displayed.
Connectors
A screwless system from the manufacturer WAGO Kontakttechnik is used as the connector. The 1-wire female connectors are 100% protected against mismating and have an eject and locking mechanism. All conductor types up to 1.5mm² can be connected.
Software and control
Our DELIB driver library, which is included with the product, makes it easy to address the product via our API.
We offer support for the following programming languages:
- C
- C++
- C#
- VB
- VBA
- VB.Net
- Java
- Delphi
- LabVIEW
We offer support for the following operating systems:
- Windows 10 (32bit/64bit)
- Windows 8/8.1 (32bit/64bit)
- Windows 7 (32bit/64bit)
- Windows Vista (32bit/64bit)
- Windows XP (32bit/64bit)
- Windows Server 2003 (32bit/64bit)
- Windows 2000
- Linux
Corresponding programming examples can be found in the “Software” section of the products or are included on the driver CD.