RS-232/RS-485 Module with 8 * PT100 Inputs (galvanically isolated)
RO-SER-PT100-8
RS-232/RS-485 Module with 8 * PT100 Inputs (galvanically isolated)
- RS-232/RS-485 interface controlled PT100 module
- 8 * PT100 sensors inputs, galvanically isolated
- LED status indication per input state
- DIN rail module
- Pluggable terminal block
The RS-232/RS-485 switching modules are designed for industrial use in switchboards for measuring, controlling and operating. Every module has a RS-232/RS-485 interface and is therefore easily connected to a serial port (e.g. PCs, terminal PCs ...). The RS-232/RS-485-bus has proven itself during many years and points to its high flexibility.
The particularity hereby is the concept of galvanic isolation of the RS-232/RS-485 interface. The galvanic isolation protects against voltage peaks.
Over the two-or three-wire input a PT100 sensor can be connection. A very accurate measurement is possible because of the integrated 24 bit A/D converter. Depending on the sensor the temperature rainge is from -200°C to 850°C.
The resistivity is determined by an additional sensor cable and balanced, so that the use of a much longer cable is possible
As terminal block, user-friendly terminal strips with locking protection and ejection mechanism are used. They allow quick replugging . The wire connection itself is realised with a screwless connector system. A tool is included with each module.

More info
RS-232/RS-485-interface
RS-232/RS-485-interface connection (galvanic isolated)
By using a 9 pin D-SUB connector the module will be connected to the PC or any other device using a serial interface.The module interface is galvanic isolated from connected devices by using an optocoupler.
Inputs
Visual monitoring of inputs
The state of every input is directly indicated by a LED. That way, wrong wiring is easily noticeable.
- Activity LED (short blink for interface communication)
- Status LED (short blink when accessing PT100)
- Access LEDs for all PT100 inputs (short blink if PT100 sensor is connected. Permanent on when inputs are missing or a defective PT100 sensor is connected)
Detecting accurate temperature
Because of the 24 bit A/D converter, accurate measurements are possible. The PT100 modul is able to detect the change of the electrical resistance of the PT100 sensor. The resistivity is determined by an additional sensor cable and balanced, so that the use of a much longer cable is possible. Depending on the sensor the temperature rainge is from -200°C to 850°C.
Connector
Easy to maintain connector system
The plug and socket consist of a multipoint socket connector and a multipin connector with a throw-off lever. Plug-in and plug-out is easy as well as rewiring the terminal strip. The wire connection itself is realized with a screwless connector system. A tool is included with each module.

Config
Configuration of the RS-232/RS-485 Module
A brand new serial module is delivered in RS-232 mode. To change this mode to RS-485, you just have to open the case and place some jumper. Detailed information can be found in the manual RO-Serie
RS-232/RS-485 parameter configuration
All serial parameter can be configured by a few DIP switches. Such as baudrate, module address, special-mode and other interface specifications.
The special-mode allows you to set the module on constant values. This may be useful for a quick start-up and defect analysis.

Tech.-Info
RS-232 / RS-485-Interface |
|
| Power Supply | 7V bis 24V DC (über zweipolige steckbare Schraubklemme) |
| Interface |
RS-232/RS-485 (galvanic isolated using optocoupler) Connection by 9 pin. D-SUB socket One LED for each 3,3V and 5V Voltage feed Baud rate: 1,25 MBit - 300 Bit |
| Control-LED |
RS-232/RS-485 -activity ERROR Input state change (only for digital outputs) Timeout (only for outputs) I/O Module access |
PT100-Modul |
|
| Inputs |
8 * PT100-Inputs, galvanic isolated 24 bit A/D converter for accurate measurements Temperature range form 200°C - 850°C |
| Activity-LED |
Activity LED (short blink on communication on the interface) Status LED (short blink on accessing the PT100) Access LEDs for all 8 * PT100 inputs (short blink if PT100 sensor is connected. Permanent on when inputs are missing or a defective PT100 sensor is connected) li> |
| Connectors | 10 pin pluggable terminal block for 8 * PT100 channels |
General |
|
| Operating temperature | +10°C...+50°C |
| Dimensions | 126 mm x 126 mm x 31 mm (LxBxH) |

Diagrams
Functionality of the product.


Software
Controlling of our RS-232/RS-485 modules
Our RS-232/RS-485 modules can be controlled by two different ways.
1. The Windows driver library DELIB
The DELIB driver library allows a direct communication of our modules. You don't have to worry about the Handshake and the serial protocoll. The DELIB DLL assumes it for you!
2. You may program the controlling software by yourself
In our download area you can find a conform protocol. So our serial modules can be connected to small Linux computers or workstations for engineering, with RS-232/RS485 Interface.
Controlling by the DELIB driver library under Windows
The extensive but easy handling library is written for computer language, which responds to DLL's. Programming examples in source code for C, Delphi or Visual Basic can be found in our download area.
Examples for responsing our products with "C"
In the following example we show you in "C", how to access to our input modules in short time.
1. Step: Open the module
handle = DapiOpenModule(RO-SER,0); // Open serial module
2. Step: Reading of 16 digital inputs
data = DapiDIGet16(handle, 0); // Read the first 16 digital inputs
3. Step: Close the module
DapiCloseModule(handle); // Close the module
The function "DapiOpenModule" is used to open a special kind of module.
Which module should be openend, is defined by the two parameters.
The first parameter is for the "module ID". By the integrated "DELIB.H", you can also set this parameter to "RO-SER".
So the driver library recognize, that a serial interface will be driven.
The second parameter assigns the module number. If only one module is connected to the pc, the module number is "0". Are there more than one module in the network, you have to set the correct number.
The link to the according IP-address of the module can be configured by the "DELIB-Configuration Utility".
Testprogram with examples for digital inputs
| Digital Input/Output Sample Testprogramm für Module |
|
Click to enlarge ![]() |
With this program you can test our modules very easily. The digital input/output sample testprogram is easy to use and supports all of our measurement modules. The example above shows the test of a RO-USB-O32 input module.
Controlling by the open source ethernet protocol
If required, you can program your own controlling software. The according communication protocol is disclosed. The modules will be controlled by register. Therefore we designed an open source communication protocol, which allows to respond to the modules and excecute read/write commands.
The manual "Serial Protocol" describes transmission and receiving frames, to communicate with our serial modules.

Overview about available DELIB-Functions
General
General Handling
DapiOpenModule
ULONG DapiOpenModule(ULONG moduleID, ULONG nr);
This function opens a particular module. p>
DapiCloseModule
ULONG DapiCloseModule(ULONG handle);
This command closes an opened module. p>
DapiGetLastError
ULONG DapiGetLastError();
This function returns the last registered error. p>
DapiGetLastErrorText
ULONG DapiGetLastErrorText(unsigned char * msg, unsigned long msg_length);
This function reads the text of the last registered error. p>
DapiGetDELIBVersion
ULONG DapiGetDELIBVersion(ULONG mode, ULONG par);
This function returns the installed DELIB version. p>
Special
Special functions
DapiSpecialCommand - DapiSpecialCMDGetModuleConfig
ULONG DapiSpecialCommand(ULONG handle, DAPI_SPECIAL_CMD_GET_MODULE_CONFIG, par, 0, 0);
This command returns the hardware equipment (number of in-/output channels) of the module. p>
Analog-input
Analog input functions
DapiTempGet
float DapiTempGet(ULONG handle, ULONG ch);
Dieser Befehl liest einen Temperatur Kanal. p>

Connector
Plug connection
Screwless plug connectors
All input and output connectors have a practical, screwless terminal block. An mechanic ejection guarantees a very quick module change without any special tools. Wire connection happens with screwdriver or an included plastic pin. (s. pic.1)
Pic1:
Connection example of a RO-Module
![]() |
RO-MODULE | |
![]() |
Step 1:
| |
![]() |
Step 2:
| |
![]() |
Step 3:
| |
![]() |
Step 4:
|

Optional E.
Hutschiene-1m
Die 1m Hutschiene eignet sich optimal zur schnellen Montage unserer Steuer/Regeltechnik-Module.
Netzteil 24V/2A für Hutschinenmontage
Das Hutschienen-Netzteil bietet Anwendern eine sichere Arbeitsumgebung und ist eine ideale Spannungsversorgung für unsere Steuer/Regeltechnik-Module. Es besitzt einen Wirkungsgrad von bis zu 80% und Internationale Sicherheitszulassungen Dank der Isolationsklasse 2 als auch der Sicherheit die das Hutschienen-Netzteil bietet.
10 poliger Steckverbinder mit Auswerfmechanik
Unsere Steckverbinder bieten einen einfachen und sicheren Anschluss an unsere Module. Durch die integrierte Auswerfermechanik ist das nachträgliche Austauschen der angeschlossenen Module möglich.

Manuals
Manuals
Manual RO-Series
Manual RO-Series Technical hardware manual for the whole RO-Serie
- Description of the measurement modules
- Configuration of the different module interfaces
- Installation of the DELIB driver library
Manual RO-SER-INTERFACE
Manual RO-SER-INTERFACE (Extract of the Manual RO-Series)Software documentation of our RO-SER-Interfaces
Manual RO-Register Assignment
Manual RO-Register Assignment
- Description accessing the registers
- Description of the input, ouput and configuration registers
- Installing the DELIB driver library
Manual RO-SER Transfer Protocol
Manual RO-SER Transfer Protocol Description of the send and receive frame to communicate with the RS-232/RS-485 modules
Datasheets
Datasheets
Driver
Driver / Programs
Manual for DELIB Driver Library for Windows 7, Windows Vista, XP, 2000 and Linux
Manual for DELIB Driver Library for Windows 7, Windows Vista, XP, 2000 and Linux Documentation of all functions
- module open/close functions
- Digital Input read 1 / 8 / 16 / 32 / 64 bit
- Digital Output write 1 / 8 / 16 / 32 / 64 bit
- A/D Read, read_volt, read_mA, set A/D mode
- D/A Write, write_volt, write_mA, set D/A mode
DELIB driver library for Windows 7, Vista, XP and 2000
DELIB driver library for Windows 7, Vista, XP and 2000
Installation file for USB driver
supports the following operating systems: 32 Bit:
- Windows 7
- Windows Server 2008
- Windows Vista
- Windows XP
- Windows Server 2003
- Windows 2000
64 Bit:
- Windows 7 x64
- Windows Server 2008 x64
- Windows Vista x64
- Windows XP x64
- Windows Server 2003 x64
Downloads
Downloads
RO Flasher Update